IVAR MULTIMIX Instrucciones Para Una Correcta Instalación página 8

Sistema modular para centrales térmicas de zonas
Ocultar thumbs Ver también para MULTIMIX:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 26
MULTIMIX MODULAR SYSTEM FOR ZONE THERMAL POWER STATIONS
1. MULTIMIX MAIN COMPONENTS
The elements which characterise the MULTIMIX may be of three typologies:
separator-manifold, high temperature distribution kit and mixing kit.
Figure 1
The MULTIMIX system's kits come complete with GRUN03
traditional circulators or, upon request, GRUN04 electronic
circulators. If replacing the circulators, their installation
upon the MULTIMIX unit must be performed in accordance
with the following instructions. Before installing, intercept
the pump using the ball valve indicated by point 1 in Fig-
ure 2-a.
1. Push hub 2 downwards (Figure 2-b);
2. Position the circulator, making sure that the flat
seals are present on both of the connections;
3. Connect the suction hub to the circulator's suction
connector and tighten the swivel nut to seal the
connection;
4. Connect the output by raising hub 2 until it makes
contact with the circulator's output connector, then
tighten the swivel nut to seal the connection;
5. Complete the installation operations as specified in
the circulator's instruction manual;
6. Open the interception ball valve to restore the func-
tionality of the circuit.
EN
Instructions for correct installation
The installation and commissioning of the MULTIMIX system must be performed by qualified personnel in ac-
cordance with the national guidelines and/or the relative local requirements. If the operator must perform any
interventions which could pose a risk of direct contact with the boiler fluid, he/she is advised to use adequate
personal protection equipment (PPE). It is important that the instructions provided below be followed in order to
avoid damage to the system and/or personal injury.
EN
1. Automatic relief valve
2. Red ball valve (boiler fluid intake)
3. Blue ball valve (boiler fluid return)
4. Thermo-pressure gauge
5. Adjustable primary by-pass with hydraulic
separator function
6. Mixing valve
7. Secondary balancing by-pass
8. Pump interception ball valve
9. Circulator pump
10. Fixed-calibration safety thermostat
11. Differential overpressure by-pass
12. Check valve
13. Temperature sensor lodging
14. Delivery thermometer
15. Return thermometer
16. Delivery thermometer
17. Differential overpressure by-pass
18. Return thermometer
19. Pump interception ball valve
20. Check valve
21. Circulator pump
Figure 2

Publicidad

Tabla de contenido
loading

Productos relacionados para IVAR MULTIMIX

Tabla de contenido