8a
Power Metering/Monitoring Module Operation Manual (INCOM)
The 600V INCOM PM3 requires 24VDC auxiliary
power to be applied.
The 480V INCOM PM3 does not require 24VDC
auxiliary power to be applied. The built in Power
Supply will operate from 156VLL (208VLL -25%)
to 600VLL (480VLL +25%).
Caution: overvoltage will damage the unit.
Statement of Accuracy
Current - 0.5% of reading from 0.3A to 630A.
Voltage - 0.5% of reading from 35VLL to 600VLL.
Real Power - 1% of reading at an Apparent
Power Factor greater than 0.03.
Reactive Power - 1% of reading at an Apparent
Power Factor less than 0.97.
Metered values will be invalid below 35VLL.
Metered values will be zeroed below 0.3A or
10VLL.
INCOM Wiring
Please refer to TD 17513 for Wiring
Specifications
PXG Gateway
EDS Datasheet can be downloaded from
www.eaton.com
PM3 Setting Instructions (INCOM) Continued.
EATON CORPORATION www.eaton.com
IMPACC Commands
(300) Fast Status
(301) Extended Status/Reason Buffer
(303) All Standard Buffers
(305) Current Buffer
(306) Line-to-Line Voltage Buffer
(307) Line-to-Neutral Voltage Buffer
(30B) Saved Active Energy Buffer
(30C) Saved Reactive Energy Buffer
(30F, N=00:00:00) Supported Standard Buffer List
(30F, N=00:00:03) Current Buffer
(30F, N=00:00:04) Line-to-Line Voltage
(30F, N=00:00:05) Line-to-Neutral Voltage
(30F, N=00:00:06) Total Power Buffer
(30F, N=00:00:07) Per-Phase Power Buffer
(30F, N=00:00:08) Energy Buffer
(30F, N=00:00:23) Saved Energy Buffer
(30F, N=00:03:E8) Standard ASCII Device ID
(3A4) INCOM Slave-Interface Statistics
(3A7) Checksum of Previous Data Buffer
(3A8) Change Notification
Subnetwork Commands (NOTE: Subnetwork
address is fixed at 1)
(3D1) (300) - Subnetwork Fast Status
(3D1)(301)-Subnetwork Extended Status
Slave Action Commands
(3D0, N=00:00:03) Reset Power-Up Indication
(3D0, N=00:00:80) Snapshot Energy
(3D0, N=03:00:02) Reset Slave-Interface
Statistics
Broadcast Commands
(D00) Save Energy Buffer Request
Please refer to IL 17384 for description of
Commands