Adjusting the response time:
Adjustment of the response time allows adaptation of the detection sensitivity of the barrier
environment. A long response time reduces the sensitivity
Response
time
5

FINAL TESTS

After installation, verify correct operation with a complete test:
• Transmitter active: green Led on
• Alarm triggered by passage between beams: red Led on.
6

TROUBLESHOOTING

Malfunction
Green Led on transmitter out
Red Led on the receiver column
out continually
Red Led on the receiver column
lit continually
Beams interrupted, but red light
of reception column not on
50 ms
100 ms
Probable cause
Improper power supply
Transmitter column without
power
Poor alignment
Transmitter on different
channel
Channel not validated
Object obstructing the beams
The beams are not interrupted
simultaneously
200 ms
(default value)
- 17 -
400 ms
700 ms
Solution
Check power supply (operating
range between 10V and 14V).
Check transmitter power supply
Reperform alignment procedure
Change transmitter channel
Switch column power off and on
Disengage the beam axes
Interrupt all beams
simultaneously
UNIRIS II 50