Wiring the eSiren
SHOCK HAZARD: To avoid electrical shock, do not connect wires when
the circuits are energized.
The eSiren is factory‑set for 120 Vac operation. For 240 Vac
NOTE:
operation, move switch
(Figure 6).
To extend wire for the power connections, use only 12 AWG
to 18 AWG (2.5 mm
connector must be suitably protected to prevent damage.
To wire the eSiren:
1.
Strip no more than 0.25 inch (6 mm) of wire insulation from
the ends of the power leads. If you are using stranded wire, be
sure that there are no loose strands outside the connector plug
that could touch the adjacent lead and cause a short circuit.
Torque the terminal screws to 4.4 in‑lb (0.5 Nm) maximum.
2.
Connect the power source hot, neutral, and earth ground wires
as shown in Figure 6.
Figure 6 120 Vac/240 Vac power supply board
Power
Input
AC Power
Connector
3.
Plug the AC power connector into the power input connector
on the printed circuit board.
Installation and Maintenance Instructions
to the 240 Vac position
S1
to 1.0 mm
2
AC
L1 HOT
L2 NEUTRAL
GROUND
Model eSiren
) wire. The external leads and
2
240
120
120 Vac / 240 Vac
Switch, S1
13