Catalog Number • Numéro de Catalogue • Número de Catálogo: DT-355
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
DT-355-U is BAA and TAA compliant (Product produced in the U.S.)
The Wattstopper DT-355 360° Dual Technology occupancy sensors combine advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combination of these technologies helps to eliminate false triggering problems even in difficult
applications.
The DT-355 turns lighting systems on and off based on occupancy and ambient light levels. The light level feature can be used to keep
lights from turning on if the ambient light level is sufficient.
The DT-355 offers numerous operating modes that can be combined to create the ideal custom control. The sensors can be configured
to turn lighting on, and hold it on as long as either or both technologies detect occupancy. After no movement is detected for the user-
specified time the lights are switched off. A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30
seconds of an occupancy detection. The DT-355 operates on 120VAC, 230VAC (1Ø), 277VAC, or 347VAC line voltage.
Depending upon obstacles such as furniture or room layout, the area of
coverage may be less or more than the sensing distances shown in the
coverage pattern. This must be considered when planning the number of
sensors and their placement. It is also recommended to place the sensor at
least 4 to 6 feet away from air supply vents.
Mount the sensor to the ceiling. The DT-355 is designed for a ceiling heights of
about 8-12 feet. Mounting above or below this range will significantly affect the
coverage patterns. As a general rule, each occupant should be able to clearly
view the sensor.
Masking the PIR Lens: Opaque adhesive tape is supplied so that sections
of the PIR lens can be masked. This restricts the sensor's view and allows
you to eliminate PIR coverage in unwanted areas such as hallways outside
of the desired coverage area. Since masking removes bands of coverage,
remember to take this into account when troubleshooting coverage problems.
The Ultrasonic coverage cannot be masked, but you can adjust its sensitivity
to reduce the coverage area.
Wattstopper
360° Dual Technology • Line Voltage Occupancy Sensor (version 3)
with Light Level feature
Double technologie à 360° • Détecteur de mouvement de tension de ligne (v3)
avec les fonctionnalités de niveau de luminosité
Doble tecnología de 360° • Sensor de ocupación de voltaje de línea (v3)
con nivel de luz
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltages ....................................................................120//230/277/347VAC, 50/60Hz
Load Requirements
@120VAC .......................................................... 0-800W Ballast/Tungsten/LED
@230VAC (Single Phase) ................................................0-1200W Ballast/LED
@277VAC ........................................................................0-1200W Ballast/LED
@347VAC ........................................................................0-1500W Ballast/LED
Operating Temperature ...................................................... 32° to 131°F (0° to 55°C)
Terminal Torque Rating ........................................... 4.428 inch pound-force (0.5Nm)
Ballast Operating Temperature ........................................... 32° to 131°F (0° to 55°C)
Light Level One-Step Adjustment ..........................................................10FC–300FC
Time Delay Adjustment ..................................................... 30 seconds to 30 minutes
Walk-Through Mode ............................................ 3 minutes if no activity after 30 sec
Test Mode ......................................................................5 sec. upon DIP switch reset
PIR Coverage (Typical) ................................................................................. 1300 ft2
Sensitivity Adjustment ............................................. High or Low (DIP switch setting)
Ultrasonic Coverage (Typical) ....................................................................... 1300 ft2
Sensitivity Adjustment .............................................................. Min. to Max. (trimpot)
Frequency ........................................................................................................ 40kHz
UNIT DESCRIPTION
PLACEMENT GUIDELINES
®
SPECIFICATIONS
36'
36'
20%
Ultrasonic
Overlap
Sensor
If the space is larger than 30' x 30' it will be necessary to
use more than one sensor to ensure complete coverage.
PIR
Coverage
36 ft
(10.97m)
Ultrasonic
Coverage
36 ft
(10.97m)
20%
Ultrasonic
Overlap