Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

No: 24139 – 06/17 rev. 2
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: HB330-B, HB340-B, HB350-B, HB350C-B
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
HB3x0-B L1
The HB3x0 occupancy sensors are designed for automatic lighting control in warehouse high bay applications. All models contain a
passive infrared sensor (PIR). The HB3x0-B series sensors are modular and are made up of two parts, a Power Module (HB3x0-B) and
a Lens (HBLx). The coverage area is determined by the lens module. The lenses are interchangeable with any HB3xx series sensor.
See the HBLx Lens Coverage Guide, available at http://www.legrand.us/wattstopper for more information.
All models in the HB3x0-B series use a set of DIP switches to set the time delay, PIR sensitivity, and occupancy sensing overrides.
• The HB330 contains two relays for controlling both phases of a 208VAC or 240VAC load.
• The HB340 contains two relays for controlling both phases of a 480VAC load or a single 347VAC load.
• The HB350 provides a single load controlling relay.
• The HB350C-B is for colder ambient temperature applications: -40° to 131°F (-40° to 55°C)
Coverage patterns, density and range, are determined by the type of Lens attached to the HB3x0-B.
For a complete description of each lens coverage pattern, see the HBLx Lens Coverage Guide.
1. Determine the mounting location appropriate to the features of the
power module and the coverage area. Careful consideration must be
given to sensor placement. Avoid placing the sensor where shelving or
other obstructions may block the sensor's line of sight.
2. Make sure that you have the appropriate accessories for the sensor
mounting configuration. (See Mounting Options.)
3. Assemble any necessary mounting accessories and attach them to the power module, making sure that the flying leads from the
power module are accessible.
4. Connect the line voltage and load wires to the power pack leads as shown in the Wiring Diagram for the unit's application.
• Do not allow bare wire to show.
• Make sure all connections are secure.
5. Attach the Lens to the HB3x0-B.
6. Restore power from the circuit breaker.
HB3x0-B L2/
HB3x0-B L3
HB3x0-B L7
DESCRIPTION AND OPERATION
Wattstopper
High Bay • Low Voltage • Passive Infrared Occupancy Sensor Power Module
Grande hauteur • Basse tension • Infrarouge passif Module d'alimentation
du détecteur de présence
Módulo de alimentación •de bajo voltaje • para el sensor de ocupación
infrarrojo pasivo para áreas de almacenamiento elevadas
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
HB330-B Power Module
Voltage ................................................ 208/240VAC, 60Hz
Load Ratings (each relay)
HB340-B Power Module
Voltage ................................................ 347/480VAC, 60Hz
Load Ratings
HB350-B Power Module
Voltage ................................................ 120/277VAC, 60Hz
Load Ratings (each relay)
U.S. Patents: .............................5,640,113 and 5,804,991
COVERAGE
INSTALLATION
®
SPECIFICATIONS
@ 208VAC, 60Hz ................................. 5AMP ballast
@ 240VAC, 60Hz ................................. 5AMP ballast
@ 347VAC, 60Hz ................................. 5AMP ballast
@ 480VAC, 60Hz ................................. 5AMP ballast
@ 120 VAC, 60Hz .......... 0-800W ballast or tungsten
@ 277 VAC, 60Hz ............................0-1200W ballast
@ 120 VAC ......................................................1/6 hp
WARNING: TURN THE POWER
OFF AT THE CIRCUIT BREAKER
BEFORE WIRING THE SENSOR.

Publicidad

Tabla de contenido
loading

Resumen de contenidos para LEGRAND Wattstopper B330-B

  • Página 1 Lens (HBLx). The coverage area is determined by the lens module. The lenses are interchangeable with any HB3xx series sensor. See the HBLx Lens Coverage Guide, available at http://www.legrand.us/wattstopper for more information. All models in the HB3x0-B series use a set of DIP switches to set the time delay, PIR sensitivity, and occupancy sensing overrides.
  • Página 2: Mounting Options

    WIRING Use the wiring diagram below that is appropriate for your application of the HB3x0-B. HB330 HB340 208/240VAC Wiring 347VAC Wiring Black Red (Load A) Phase A Black Red (Load A) Neutral Line Load Load Black w/White Stripes Red w/White Stripes (Load B) Phase B Black with White Stripes Neutral...
  • Página 3 The HBEM3 extender module allows threading the wires Mounting to Fixture with through its chase nipples and into the fixture for connection. HBNB3 and HBEM3 The two sides of the HBEM3 are then snapped together to protect the wires. The short chase nipple is designed to snap HBEM3 into the HBNB3 connection box while the longer chase nipple Extender...
  • Página 4: Ordering Information

    IMPORTANT START-UP INFORMATION When the power module is installed and power is connected, the load comes ON and stays ON for 50 seconds. This warm-up period only occurs during installation or after a power failure of 5 minutes or more. •...
  • Página 5 HB340-B Module d’alimentation HB3xx. Consultez le Guide des Portées des lentilles HBLx, Tension ..........347/480VCA, 60Hz disponible sur http://www.legrand.us/wattstopper pour plus Capacité des charges d’informations. @ 347VCA, 60Hz ......... 5AMP ballast Tous les modèles de la série HB3x0-B utilisent un ensemble de @ 480VCA, 60Hz .........
  • Página 6: Options De Montage

    OPTIONS DE MONTAGE Le HB3x0-B peut être monté soit directement sur la surface du Le montage du coffret arrière HBNB3 nécessite une entrée luminaire via les deux orifices à vis du module d'alimentation défonçable standard de 12,7 mm (1/2 po) pour le manchon de soit en utilisant le coffret arrière HBNB3 et un manchon traversée.
  • Página 7 RÉGLAGES Le détecteur est préréglé en usine comme suit : Sensibilité PIR (interrupteurs 1 et 2) Moyen 85 % Temporisation (interrupteurs 3-7) 15 minutes Dérogation IRP (interrupteur 8) ARRÊT Sensibilité de l’IRP (interrupteurs 1 et 2) Interrupteur Il peut être nécessaire de régler la sensibilité de l’IRP en cas SENSIBILITÉ...
  • Página 8 Les lumières ne s’éteignent pas : 1. S’il n’y a aucun mouvement de personnes ou équipement dans le champ de vision du détecteur, mais que la DEL rouge clignote, cherchez une source proche d’énergie infrarouge en mouvement, telle que de l’air turbulent projeté par un appareil de chauffage ou de refroidissement, ou d’autres sources.
  • Página 9: Especificaciones

    HB340-B Módulo de alimentación la Guía de cobertura de la lente HBLx, disponible en Voltaje ..........347/480VCA, 60Hz http://www.legrand.us/wattstopper para obtener más información. Especificaciones de carga Todos los modelos de la serie HB3x0-B utilizan un conjunto de @ 347VCA, 60Hz ........ 5AMP balasto interruptores DIP para ajustar el tiempo de retardo, la sensibilidad @ 480VCA, 60Hz ........
  • Página 10: Opciones De Montaje

    OPCIONES DE MONTAJE El montaje en la caja posterior HBNB3 requiere un troquel de 12 El HB3x0-B puede conectarse directamente a la superficie del accesorio de iluminación a través de los dos orificios para mm (1/2 in) estándar para el empalme roscado. La caja viene lista tornillos provistos en el módulo de alimentación o utilizando para el montaje lateral.
  • Página 11: Solución De Problemas

    AJUSTES La configuración de fábrica del sensor es la siguiente: Sensibilidad del PIR (interruptores 1 y 2) Medio 85 % Retardo (interruptores 3 a 7) 15 minutos Anulación del PIR (interruptor 8) APAGADO Sensibilidad del PIR (interruptores 1 y 2) Interruptor Es posible que sea necesario ajustar la sensibilidad del PIR si hay SENSIBILIDAD DEL PIR...
  • Página 12: Información Para Hacer Pedidos

    No. 24139 – 06/17 rev. 2 © Copyright 2017 Legrand All Rights Reserved. 800.879.8585 © Copyright 2017 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2017 Legrand Todos los derechos reservados.

Este manual también es adecuado para:

Wattstopper hb340-bWattstopper hb350-bWattstopper hb350c-b

Tabla de contenido