UNIT DESCRIPTION
The WattStopper DT-305 360° Dual Technology occupancy
sensors combine advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combination of these technologies
helps to eliminate false triggering problems even in difficult
applications.
The DT-305 turns lighting systems on and off based on
occupancy. The DT-305 provides numerous operating modes that
can be combined to create the ideal custom control. The sensors
can be configured to turn lighting on, and hold it on as long as
either or both technologies detect occupancy. After no movement
is detected for a user specified time (30 seconds to 30 minutes)
the lights are switched off. A "walk-through" mode can turn
lights off after only 3 minutes, if no activity is detected after 30
seconds of an occupancy detection.
The DT-305 operates on 24V, supplied by WattStopper Power Packs.
COVERAGE PATTERN
The DT-305 provides a 360° coverage pattern. The coverage shown represents walking motion at a mounting height of 8-12 feet. For
building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease. The coverage for PIR ONLY
trigger mode varies with mount height. Refer to pattern below for details. Ultrasonic coverage is roughly the same for 8-12 foot mount
heights. Refer to PIR and Ultrasonic trigger mode coverage for details.
0
8ft
(2.4m)
10ft
(3.0m)
12ft
(3.7m)
40ft
30ft
20ft
(12.2m)
(9.1m)
(6.1m)
PIR Only Coverage
PLACEMENT GUIDELINES
Depending upon obstacles such as furniture or room layout, the area of coverage may be less or more than the sensing distances
shown in the coverage pattern. This must be considered when planning the number of sensors and their placement. It is also
recommended to place the sensor at least 4 to 6 feet away from air supply vents.
Mount the sensor to the ceiling. The DT-305 is designed for a ceiling heights of about 8-12 feet. Mounting above or below this range will
significantly affect the coverage patterns. As a general rule, each occupant should be able to clearly view the sensor.
Masking the PIR Lens: Opaque adhesive tape is supplied so that sections of the PIR lens can be masked. This restricts the sensor's
view and allows you to eliminate PIR coverage in unwanted areas such as hallways outside of the desired coverage area. Since masking
removes bands of coverage, remember to take this into account when troubleshooting coverage problems. The Ultrasonic coverage
cannot be masked, but you can adjust its sensitivity to reduce the coverage area.
Common application: Classroom: Position the sensor
so that the maximum coverage is achievable. Be sure
that the sensor is not pointing out the door.
Sensor
360° Dual Technology • Low Voltage Occupancy Sensor
Double technologie à 360° • Détecteur de présence basse tension
Doble tecnología de 360° • Sensor de presencia de bajo voltaje
Side View
10ft
0
10ft
20ft
(3.0m)
(3.0m)
(6.1m)
36'
36'
SPECIFICATIONS
Voltage ............................18-28VDC/VAC, half wave rectified AC
Current Consumption .......................................................25 mA
Power Supply ....................................WattStopper Power Packs
Isolated Relay Rating ........................................1A @30VDC/VAC
Operating Temperature....................... 32° to 131°F (0° to 55°C)
Time Delay Adjustment ......................30 seconds to 30 minutes
Walk-Through Mode ...........3 minutes if no activity after 30 sec
Test Mode ...................................... 5 sec. upon DIP switch reset
PIR Coverage (Typical) ................................................... 1300 ft2
Sensitivity Adjustment .....High or Low (DIP switch setting)
Ultrasonic Coverage (Typical) ........................................ 1300 ft2
Sensitivity Adjustment .................. Min. to Max. (trimpot)
Frequency............................................................... 40kHz
UL & CUL Listed for use with WattStopper Power Packs
PIR
30ft
40ft
Coverage
(9.1m)
(12.2m)
Ultrasonic
Coverage
36 ft x 36 ft
(10.97m x 10.97m)
If the space is larger than 30' x 30' it will be necessary to
use more than one sensor to ensure complete coverage.
36'
36'
20%
Ultrasonic
Overlap
Sensor
DT-305
with Manual On feature
avec les fonctionnalité de marche manuelle
con función de encendido manual
Top View
8-12 foot Mounting Height
20%
Ultrasonic
Overlap
version 3
Drawings
not to scale,
representative
of PIR and
Ultrasonic
Trigger Mode
major motion
36 ft
coverage
(10.97m)
PIR
Coverage
36 ft
(10.97m)
Ultrasonic
Coverage
36 ft
(10.97m)

Publicidad

loading

Resumen de contenidos para LEGRAND DT-305

  • Página 1 4 to 6 feet away from air supply vents. Mount the sensor to the ceiling. The DT-305 is designed for a ceiling heights of about 8-12 feet. Mounting above or below this range will significantly affect the coverage patterns.
  • Página 2 TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS, SWITCHES OR SENSORS. DT-305 02829r4 360° Dual Technology Each WattStopper BZ series power pack can supply power for 5 DT-305 sensors. When Occupancy Sensor LISTED PIR & 40kHz Ultrasonic 88T9 +24VDC/VAC using more sensors than this, multiple power packs are required.
  • Página 3 Settings 6 7 8 Standard The DT-305 has 8 logic configurations for occupancy triggers, set with DIP switches 6, 7 & 8. Determine the Option 1 appropriate Occupancy Logic Option using the Trigger matrix, then set the DIP switches accordingly.
  • Página 4 Power Pack: 120/277 VAC, 50/60Hz, 225mA, 20A ballast/ELV/MLV/incandescent/LED;16A E-ballast/CFL S120/277/347E-P Auxiliary Relay Pack: 120/277VAC, 60Hz, 20A Ballast, 347VAC, 60Hz, 15A Ballast All sensors are white. BZ series power packs supply power for up to 5 DT-305 sensors. Call 800.879.8585 for Technical Support...
  • Página 5 Montez le détecteur sur le plafond. Le DT-305 est conçu pour une hauteur de plafond d’environ 2,44 à 3,66 m (de 8 à 12 pi). Le placer à une hauteur supérieure ou inférieure à celle recommandée affectera de manière significative la portée de l’appareil. En règle générale, chaque occupant doit être capable de voir clairement le détecteur.
  • Página 6 LISTED PIR & 40kHz Ultrasonic 88T9 +24VDC/VAC Appliance Control Connect to WattStopper 5 détecteurs DT-305. Lorsque vous utilisez plus de 14 détecteurs, plusieurs blocs Class 2 Power Packs For Indoor Use Only Control Out. d’alimentation seront nécessaires. U.S.Patents: 5,640,113 Man. Switch Patent Pending Veuillez vous référer au schéma de câblage de la page suivante pour les procédures...
  • Página 7 • Minimum impose une réduction de la portée de détection de l’IRP. Minimum • Maximum oblige le DT-305 à surveiller l’environnement contrôlé et à choisir automatiquement la Maximum sensibilité maximum qui garantit un fonctionnement fiable sans fausse détection. Ce réglage est constamment mis à...
  • Página 8 2. L’activation de l’interrupteur manuel tandis que la charge est ACTIVÉE a pour effet de COUPER la charge. • Lorsque la charge est COUPÉE manuellement, elle reste COUPÉE aussi longtemps que le détecteur continue de détecter une présence. Pendant la durée de la temporisation après la dernière détection de présence, les lumières restent éteintes et le détecteur revient en mode marche automatique.
  • Página 9 Description DT-300 Détecteur de présence à double technologie, 360° basse tension avec relais isolé et détecteur du niveau de luminosité DT-305 Détecteur de présence à double technologie, 360° basse tension BZ-50, BZ-150 Bloc d’alimentation : 120/277 VCA, 50/60 Hz, 225 mA, ballast ou incandescent 20 A, 1 HP à 120/250 VCA.
  • Página 10 También se recomienda colocar el sensor a 4 a 6 pies como mínimo de distancia de los respiraderos de suministro de aire. Montaje de sensor en cielo raso. El sensor DT-305 está diseñado para una altura de cielo raso de aproximadamente 8 a 12 pies. El montaje por encima o por debajo de este rango afectará...
  • Página 11 Cada paquete de alimentación de la serie BZ de WattStopper puede suministrar energía a Occupancy Sensor LISTED PIR & 40kHz Ultrasonic 88T9 +24VDC/VAC 5 sensores DT-305. Cuando se utilicen más sensores, se necesitarán varios paquetes de Appliance Control Connect to WattStopper Class 2 Power Packs alimentación.
  • Página 12 • El mínimo obliga un rango de detección reducido para la tecnología PIR. Sensibilidad del PIR • El máximo hace que el DT-305 supervise el ambiente controlado y que seleccione automáticamente Mínimo la sensibilidad máxima que ofrecerá un funcionamiento confiable sin falsas detecciones. Esta Carga configuración se actualiza constantemente.
  • Página 13 2. Si se activa el interruptor manual mientras la carga está encendida, esto apaga la carga. • Cuando se apaga la carga manualmente, siempre y cuando el sensor siga detectando la presencia, la carga se mantiene apagada. Después de la última de detección de presencia, las luces permanecen apagadas y el sensor se revierte al modo de encendido automático.
  • Página 14 Descripción DT-300 Sensor de presencia con doble tecnología de bajo voltaje y de 360° con relé aislado y el sensor de nivel de luz DT-305 Sensor de presencia con doble tecnología de bajo voltaje y 360° BZ-50, BZ-150 Paquete de alimentación: 120/277 V CA, 50/60 Hz, 225 mA, balasto o incandescente de 20 A, 1 HP a 120/250 V CA BZ-200, BZ-250 Paquete de alimentación: 120/277 VCA, 50/60Hz, 225mA, ballasto/ELV/MLV/incandescente/LED 20A;...
  • Página 15 Visit our website: www.wattstopper.com...
  • Página 16 WattStopper garantiza que sus productos están libres de defectos en materiales y mano de obra por un período de cinco (5) años. No existen obligaciones ni responsabilidades por parte de Legrand/WattStopper por daños consecuentes que se deriven o estén relacionados con el uso o el rendimiento de este producto u otros daños indirectos con respecto a la pérdida de propiedad, renta o ganancias, o al costo de extracción, instalación o reinstalación.