Connection Diagram, Examples Of Connections For Peripherals - ACS contsys Flowcont M Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

D184B112U04
5.3

Connection diagram, examples of connections for peripherals

Variant 01 (without display) or 03 (with display)
(pulse output passive, optooupler or
contact output passive, optocoupler)
internal
external
Pin 3
Pin 4
Pin 2
Not assigned
Pin 1
Not assigned
Variant 05 (with display)
(pulse output passive, optocoupler and contact input passive, optocoupler or
contact output passive, optocoupler and contact input passive, optocoupler)
internal
external
Pin 3
Pin 4
Pin 2
R
I
Pin 1
R
= 2 kΩ
I
Auxiliary power
(24 V AC/DC)
Pin 1
24 V AC/DC
Pin 2
GND
Pin 4
Functional earthing
Technical data of signal outputs
Pulse output, passive
(optocoupler data:)
16 V ≤ U
≤ 30 V; 0 V ≤ U
CEH
CEL
0 mA ≤ I
≤ 0.2 mA ; 2 mA ≤ I
CEH
fmax = 20 pulse/sec; pulse width 20 ms – 2550 ms
* Contact output, passive, optocoupler
The function of the optocoupler for the pulse output
can be changed over using software.
It may either function as a pulse output or contact output.
The changeover function is only available with the version with a
display!
One of the following statuses can be signalled in the "contact out-
put" function:
Inlet/outlet signalling, min./max. contact, system alarm.
If working with the version without a display, the opto-electronic
coupler function can only be set as "pulse output" or "inlet/
outlet signalling".
Fig. 11:
Examples of connections for peripherals, signal output data
Flowcont M
R
*
B
Pulse output/
contact output*
U
CE
---------- -
*R
B
I
CE
R
*
B
Pulse output/
contact output*
24 V+
0 V
≤ 2 V;
≤ 220 mA
CEL
5 Electrical connection
Variant 02 (without display) or 04 (with display)
(pulse output passive, optocoupler and
current output 0/4 −20 mA or contact output passive,
optocoupler and current output 0/4−20 mA)
internal
external
R
Pin 3
Pin 4
+
Pin 2
0/4 - 20
Pin 1
Current output
can be set to between 0/4 and 20 mA; Load ≤ 600 Ohm
Contact input
The input is considered as actuated at an external
voltage of between 16 V ≤ U
CEH
It is considered as non-actuated at a voltage level of between
0 V ≤ U
≤ 2 V DC. The internal resistance of the
CEL
contact input is: Ri = 2 kOhm.
Auxiliary power
16.8 V AC - 26.4 V AC and/or 16.8 V DC - 31.2 V DC
Ripple: 5 %
Power consumption< 5 W
*
B
Pulse output/
contact output*
≤ 30 V DC.
GB 15

Publicidad

Tabla de contenido
loading

Tabla de contenido