4 x
the type of appliance and the installation
and usage conditions.
In any case, it should be inspected at least
once a year by a qualified technician.
During maintenance operations, it is
important to verify that the drip-plate
with drain trap contains water (this
check is particularly important if the
Codice/Code 8108150
Modello/Model CLIMIT GG HE 25
Matricola/Serial n. 9999999999
PAR 1 = 02 (METANO)/ 06 (GPL)
PAR 2 = 01
1
2
generator has not been used for exten-
ded periods of time).
If necessary, the drip plate can be filled
using the tap provided (fig. 20).
Instead, to clean the exchanger and the
burner, do in the following way (fig. 20):
- Cut power from the boiler.
FLUE GAS CHAMBER
CAMERA FUMO
SLEEVE
MANICHETTA
- Empty the condensation-collecting tray.
- Remove the sleeve.
- Spray the water jet inside of the burner
and the exchanger in order to remove
dust and combustion residue.
DO NOT USE CHEMICAL AGENTS OR
STEEL BUSHES.
- Remove the condensation-collecting tray.
Clean it and put it back tightening the
fixing nuts with a torque wrench.
- Having re-assembled the tray, check its
sealing with a leak detector.
4.5. 1

Chimney sweep function

To check boiler combustion, press at the
same time the installer's key (
a few seconds.
The chimney sweep function will switch on
and will continue for 15 minutes. During the
15 minutes functioning of chimney sweep
function, pressing the keys (
take the boiler respective at maximum (Hi)
and at minimum (Lo) power. From that
moment, the boiler will start working in
heating mode at maximum power, with cut
off at 80°C and re-ignition at 70°C.
Before activating the chimney sweep func-
tion make sure that the radiator valves or
eventual zone valves are open.
The test can also be carried out with the
boiler working in D.H.W. mode.
For this, after activating the chimney sweep
function, open one or more hot water fau-
cets. Under these conditions, the boiler will
Fig. 19
function at maximum power with the
D.H.W. kept at between 60°C and 50°C.
During the test, the hot water faucets
must remain open.
For exit to the chimney sweep function
press the key
The chimney sweep function will automa-
tically switch off after 15 minutes from
the activation.
TIGHTENING TORQUE : 2 Nm
COPPIA DI SERRAGGIO : 2Nm
e
) for
and
)
of the control panel.
TRAY
VASCHETTA
Fig. 20
83
IT
ES
ENG