Fm Installation Drawing - Hart 5437 Manual Del Producto

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

FM Installation drawing 5437QF01-V5R0
FM Certificates
Division1 / Zone 0, Intrinsic Safe Installation
For safe installation of the 5431D..,5434D.., 5435D.. and 5437D.. the following must be
observed.
Marking:
Hazardous Area
CL I, Div 1, GP ABCD
CL I, Zone 0 IIC
Terminal:
3,4,5,6,7,8,9
Uo: 7.2 VDC
Io: 12.9 mA
Po: 23.3 mW
Lo: 200 mH
Co: 13.5 μF
Terminal 1,2
AEx/Ex ia IIC, T6...T4 Ga;
CL I, Div 1, Gp ABCD, T6...T4;
Ui: 30 VDC; Ii: 120 mA Pi: 900 mW
Li:0 μH; Ci:1.0 nF
Ui: 30 VDC; Ii: 100 mA Pi: 750 mW
Li:0 μH; Ci:1.0 nF
40
FM16CA0146X and FM16US0287X
CL I, Div 1, Gp A,B,C,D
CL I, Zone 0 AEx ia IIC, T6...T4
CL I, Zone 1 [0] AEx ib [ia] IIC,T6...T4
Ex ia IIC, T6...T4 Ga
Ex ib [ia Ga] IIC, T6...T4 Gb
9
8
7
+
1
6
2
5
5431D
5434D
4
5435D
3
5437D
Non Classified Area
Associated
ia
Apparatus
or
Barrier
Um ≤ 250V
Voc or Uo ≤ Vmax or Ui
Isc or Io ≤ Imax or Ii
Po ≤ Pi
Ca or Co ≥ Ci + Ccable
La or Lo ≥ Li + Lcable
Temperature Range
T4: -50 ≤ Ta ≤ 85ºC
T5: -50 ≤ Ta ≤ 70ºC
T6: -50 ≤ Ta ≤ 55ºC
T4: -50 ≤ Ta ≤ 85ºC
T5: -50 ≤ Ta ≤ 75ºC
T6: -50 ≤ Ta ≤ 60ºC
5437V103-ES

Publicidad

Tabla de contenido
loading

Productos relacionados para Hart 5437

Tabla de contenido