Positioning Function; Learning Mode; Axmart - VALPES VT+ Serie Manual De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Positioning function

Led de validation (pos. 2)
Learning mode - closed position
Learning mode - storage
Learning mode - open position

Learning mode

 Put the power on
 With the « Next Mode » and « Ok Mode » buttons, select the learning mode (the APPR led is on)
 Press « APPR Close » button to drive the valve up to its closed position and keep both « APPR Close » and
« APPR Mem » buttons pressed during 2 seconds.
 The APPR1 led blinks and lights up. The closed position is correctly recorded
 Press « APPR Open » button to drive the valve up to its open position and keep both « APPR Open » and « APPR
Mem » buttons pressed during 2 seconds.
 The APPR2 led blinks and lights up. The open position is correctly recorded
Both open and closed positions are recorded. Select positioning (POSI) mode and press « OK Mode » to confirm.
Setpoint signal
Feedback
According to its position, the actuator will provide a proportional voltage signal (0-10V) or a current signal (4-20mA). It's
possible to modify the feedback signal using the
DSBA3600 • Rév. 08/03/2018
Validation led (pos.1)
X
®
A
MART
software, but it requires changing the wiring.
ENGLISH
UK
-
+
+
-
Feedback
Setpoint
signal
signal
27

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Vt1500Vt2400Vt600Vt1000

Tabla de contenido