Troubleshooting - Mosa GE 4500 HSX Manual De Empleo

Tabla de contenido

Publicidad

© MOSA
REV.0-06/04
Problem
The motor does not start up, or
starts up and then stops
immediately
Lack of tension to the AC
sockets
Lack of tension to the AC
sockets
Trouble shooting
1) Key and start-up selector in
the wrong positions
2) Lack of or insufficient oil in
the motor
3) Faulty motor stopping device
(oil-alert)
4) Lack of fuel in tank or fuel
tap closed
5) Dirty or faulty spark plug
6) Battery not activated, low or
faulty
7) Faulty start relay
8) Cold motor
9) Other causes
1) G.F.I. switch in the OFF
position
2) Intervention of G.F.I. switch
due to faulty ground current
3) Faulty G.F.I. switch
1) Intervention of circuit breaker
(thermoprotection)
2) Faulty thermoprotection
3) Faulty alternator
Possible cause
GE 4500 HSX
Solution
1) Verify start-up procedure in
the Operating Manual
2) Refill or top off
3) Replace
4) Refill the tank. Open the fuel
tap
5) Clean
or
check
eventually replace
6) Activate,
recharge,
replace the battery
7) Replace
8) Hold down the CHOKE
button, after start-up, for a
longer period of time
9) Consult the motor Operating
Manual.
1) Position to ON
2) Disconnect load from AC
sockets.
Position the G.F.I. switch to
ON; if the switch intervenes
once again, the fault is on
board the machine.
Contrarily, the cause of the
G.F.I. switch intervention is
due to a faulty ground current
in the load or connection
cable. Find and remove the
fault.
3) Replace
1) Check total power supplied
by generator; if greater than
the power reported on the
specification nameplate,
decrease the load
2) Replace
3) Check
rotating
windings,
excitation capacitor.
See
specifc
manual.
M
40.2
and
or
diode
alternator
alternator

Publicidad

Tabla de contenido
loading

Tabla de contenido