CGB, CGD and CGE Series Connectors
Installation & Maintenance Information
APPLICATION
Eaton's Crouse-Hinds series CGB, CGD and CGE cord and cable fittings are listed for use
with flexible cord and TC, TC-ER, TC-ER-HL, ITC, ITC-ER, ITC-HL, PLTC and PLTC-ER cables
of specific sizes to provide an adequate cord or cable entrance bushing and strain relief
for internal electrical connections when assembled to standard threaded openings or
standard knockout openings. They are suitable for use in wet locations. They have not been
investigated for use in hazardous locations.
RECOMMENDATIONS FOR INSTALLATION
1.
Install body securely in conduit hub or fasten in knockout with locknut.
2.
Slide gland nut, gland washer and bushing over cable, in that order.
3.
Install cable through the body far enough to allow wire connections (see Figure 1). If
cable does not pass through the body, remove sufficient outer covering of cable to
allow conductors to pass through the connector body.
4.
Install bushing into body, slide gland washer against bushing and thread gland nut
onto body. Tighten gland nut to cause bushing to grip cable firmly so liquidtight seal
is formed.
SUGGESTED TORQUE (GLAND NUT)
Torque
Trade Size
(lb.-in.)
3/8"
200
1/2"
300
3/4"
500
1"
700
1-1/4"
1000
1-1/2"
1200
2"
1600
2-1/2"
1600
3"
1600
OPERATING TEMPERATURE
Standard neoprene seal: -25°C to +40°C
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not
guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine
the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
To avoid risk of electrical shock, electrical power must be OFF before and during
installation and maintenance of conductors.
(N-m)
22.6
33.9
56.5
79.1
113
136
181
181
181
Eaton's Crouse-Hinds Division
1201 Wolf Street Syracuse, NY 13208 • U.S.A.
Copyright© 2016
!
WARNING
Gland Nut
Gland Washer
Cable Outer
Covering
Bushing
Body
Insulated Wire
Conductors
Figure 1
IF 1826
IF 1826
Revision 1
New 10/16

Publicidad

loading

Resumen de contenidos para Eaton Crouse-Hinds CGB Serie

  • Página 1 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton’s Crouse-Hinds Division’s “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
  • Página 2 Todas las declaraciones, la información técnica y las recomendaciones contenidas en este documento se basan en informaciones y pruebas que consideramos confiables. No se garantiza que las mismas sean precisas o estén completas. En conformidad con los “Términos y condiciones de venta” de la División Crouse-Hinds de Eaton y dado que las condiciones de uso están fuera de nuestro control, el comprador debe determinar la idoneidad del producto para su uso previsto y asume todo riesgo y responsabilidad con relación al mismo.

Este manual también es adecuado para:

Crouse-hinds cgd serieCrouse-hinds cge serie