Praesideo 3.5 | Installation and User Instructions | ISO7240-16: 2007
a at least 4 characters where the display of a functional condi-
tion uses a cross-reference to other information to identify
the location;
b
at least 8 characters where the display is intended to
include the complete information on the location of a func-
tional condition.
14.9 Colours of indications
14.9. 1 The colours of the general and specific indications from
light-emitting indicators shall be as follows:
b
yellow for indications of
3
emergency loudspeaker zones in the test state.
Clause / Requirement
17 Tests
Clause / Requirement
18 Test report
Changed clauses
Clause / Requirement
4.3 Power supply
Power-supply equipment shall comply with the requirements of
ISO 7240-4 and may be internal or external to the s.s.c.i.e. cab-
inet.
The power supply may be shared with that of the emergency
detection system.
Clause / Requirement
8 Fault-warning condition
8.5 Reset of fault indications
8.5.2 Following the completion of the reset process, the indica-
tion of the correct functional conditions corresponding to any
received signals shall either remain or be re-established within
100 s.
Clause / Requirement
9 Disabled condition - Optional function
9.3 Indication of specific disablements
9.3.4 If the indication is on an alphanumeric display that cannot
simultaneously indicate all of the disablements because of its
limited capacity, at least the following shall apply.
b
Suppressed disablement indications shall be capable of
being displayed, independently of other indications, by
means of a manual operation at access level 1 or 2, which
interrogates only the disablement indications.
Bosch Security Systems | 2011-02
The test condition is an optional function and is not supported
by Praesideo. See 10.
Compliance
All tests as asked for in the clauses of section 17 have been
carried out by an accredited certification body for ISO7240-16
compliancy.
The Praesideo system has been found compliant to ISO7240-
16 and received a certification of compliancy.
Compliance
The tester must take care of documenting the testing pro-
gramme and the results of the tests in a test report that at least
contains the information as listed in clause 18.
Compliance
The installer must use power supplies and battery charging
equipment in accordance with ISO7240-4, with separate wir-
ing for mains (230Vac) and battery backup (48Vdc) from the
power supply to the Praesideo system.
The power supply equipment must be installed in a separate
cabinet, not shared with the Praesideo system, unless the com-
bination of the actual power supply equipment and Praesideo
system elements in the same cabinet has been certified.
The content of the ISO7240-16 certification is subject to
change. The most recent version of this certificate can be found
on www.boschsecurity.com.
The network controller and all amplifiers are supplied with a
mains supply and DC backup supply (48V) input. Switch over
between the both takes place automatically, without any inter-
ruption or status change other than the power supply related
indications.
The installer must ensure that the output voltages of the power
supply equipment do not exceed the specifications of the mains
and battery inputs of the connected Praesideo equipment.
Compliance
If any individual fault is reset while it is not actually resolved in
the system, the Praesideo system will report the fault again
within 100 seconds. If all faults are reset in one action, all indi-
vidual faults that are not actually resolved in the system are
reported again within 100 seconds.
Compliance
Praesideo does not support the optional function disabled con-
dition. See 9.
en | 68