Descargar Imprimir esta página

Publicidad

Enlaces rápidos

P832-LED
CAUTION: RISK OF FIRE: Recessed portions of recessed housing, other than at points of support, shall be spaced at
least ½ inch from combustible material. Thermal insulation shall not be installed within 3 inches of recessed housing or
junction box, and shall not be installed above fixture as to entrap heat and prevent the free circulation of air.
CAUTION: To complete the installation, choose only UL listed Progress trims from the label inside the housing. The use
of any trim not listed in this fixture is a violation of N.E.C. article 110-3(B) and voids all warranties.
WARNING: When using Special Control Devices with this Fixture, follow Instructions carefully to ensure N.E.C.
compliances. For more help, contact a Qualified Electrical Contractor.
Follow this instruction sheet carefully. Be sure electricity is OFF before starting installation.
1.- Cut a 4 1/2 inch diameter Hole (1) in Ceiling and pull electrical Supply Cable (2) down through opening.
CAUTION: Be careful not to cut through Joists, Wiring or Piping when cutting opening in Ceiling.
2.- Remove Cover Plate (3) from Junction Box (4). Select a UL listed Connector (5)(NOT FURNISHED) appropriate for
the Electrical Supply Cable at installation. Remove desired Knockout (6) from Junction Box (4) and secure Cable (2) to
Box with Connector (5).
3.- Connect Fixture Wires (7) to Supply Wires (8) as shown in Wiring Diagram. Replace Cover Plate (3) onto Junction Box
(4) securing in place with Cover Screw (9).
4.- Slip Fixture Assembly up through Ceiling opening with flange (11) up against Ceiling. Make sure that Straps (13) are
laying vertically against Housing (10) so that unit can pass through Ceiling opening. Loosen Wingnuts (12), rotate and
slide Straps (13) down and secure against top of Ceiling surface. Tighten Wingnuts (12).
INSTRUCTION SHEET MUST BE REMOVED FROM FIXTURE
PRIOR TO ENERGIZING.

Publicidad

loading

Resumen de contenidos para Progress Lighting P832-LED

  • Página 1 P832-LED CAUTION: RISK OF FIRE: Recessed portions of recessed housing, other than at points of support, shall be spaced at least ½ inch from combustible material. Thermal insulation shall not be installed within 3 inches of recessed housing or junction box, and shall not be installed above fixture as to entrap heat and prevent the free circulation of air.
  • Página 2 PRECAUCIÓN: RIESGO DE INCENDIO: porciones rebajadas de viviendas empotrada, excepto en los puntos de apoyo, deberán estar separados por lo menos ½ pulgada de material combustible. Aislamiento térmico no deberá ser instalado dentro de 3 pulgadas de alojamiento empotrado o caja de conexiones, y no deben instalarse por encima aparato como para atrapar el calor y evitar la circulación libre de aire.