Idiomas disponibles

5.1

Construction site

Under all circumstances, the following points must be clarified prior to installation:
The structural suitability of the ground according to DIN 18196
Maximum groundwater levels which occur and drainage capability of the subsoil
Types of load which occur, e.g. traffic loads
An expert ground report should be requested from the local planning authority to determine the physical
characteristics of the subsoil.
5.2

Trench

To ensure that sufficient space is available for working, the base area of the trench must exceed the
dimensions of the tank by 500 mm on each side; the distance from solid constructions must be at least
1000 mm.
The embankment must be designed according to DIN 4124. The construction site must be horizontal and
plane and must guarantee sufficient load-bearing capacity.
The depth of the trench must be dimensioned so that the max. earth coverage (see point 2 – installation
conditions) above the tank is not exceeded. To use the system throughout the entire year, it is necessary
to install the tank and those parts of the system which conduct water in the frost-free area. The frost-free
depth is usually approx. 600 mm – 800 mm; precise information in this regard can be obtained from the
responsible authority.
A layer of compacted, round-grain gravel (grain size 8/16, thickness approx. 150 - 200 mm) is applied as
the foundation.
5.2.1 Slope, embankment, etc.
On installation of the tank in the immediate vicinity (< 5
m) of a slope, earthen mound or slope, a statically
calculated supporting wall must be erected to absorb the
soil pressure. The wall must exceed the dimensions of
the tank by at least 500 mm in all directions, and must be
located at least 1000 mm away from the tank.
5.2.2 Groundwater and cohesive (water-impermeable)
soils (e.g. clay soil)
If it is anticipated that the tanks will be immersed deeper
into the groundwater than is shown in the adjacent
figure, sufficient dissipation must be ensured. (See table
for max. immersion depth).
Dissipation of the drainage water (e.g. via an annular
drainage system) is recommended in the case of
cohesive, water-impermeable soils.
Tank size
2700 L
Immersion
1400 mm
depth
5.2.3 Installation
adjacent
vehicles
If the underground tanks are installed adjacent to surfaces
which are used by heavy vehicles weighing over 12 t, the
minimum distance away from these surfaces is at least the
depth of the trench.
mail@graf.info
www.graf.info
5.
Installation and assembly
3750 L
4800 L
6500 L
1590 mm
910 mm
1050 mm
to
surfaces
used
by
15 / 36

Publicidad

Tabla de contenido
loading