PanelView 300 Keypad Terminals

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class II, Division
2, Groups F and G; Class III Division 2; or non-hazardous locations only. The following
WARNING statement applies to use in hazardous locations.
WARNING
!
See the nameplate on terminal for hazardous locations certifications.
ATTENTION
!
The PanelView 300 terminals have an operating temperature code of T4
(maximum operating temperature of 135°C or 275°F). Do not install the terminals in
environments where atmospheric gases have ignition temperatures less than 135°C
(275°F).

European Union Directive Compliance

If this product has the CE mark it is approved for installation within the European
Union and EEA regions. It has been designed and tested to meet the following
directives.
Publication 2711-IN027B-MU-P
EXPLOSION HAZARD
• Substitution of components may impair suitability for Class I,
Class II, Class III Division 2.
• Do not replace components or disconnect equipment unless
power has been switched off or the area is known to be
non-hazardous.
• Do not connect or disconnect components unless power has
been switched off or the area is known to be non-hazardous.
• This product must be installed in an enclosure. All cables
connected to the product must remain in the enclosure or
be protected by conduit or other means.
• All wiring must comply with N.E.C. article 501-4(b), 502-4(b),
503-3(b) as appropriate.
In Class I, Class II, Class III Division 2 Hazardous locations,
the PanelView 300 terminal must be wired per the National
Electric Code as it applies to hazardous locations. Peripheral
equipment must also be suitable for the location in which it is
installed.