7.2.6) Level two programming example (adjustable parameters)
The sequence to follow in order to change the factory settings of the parameters and adjust the average "Motor force" (input on L1 and lev-
el on L2) and increase the "Pause time" to 60" (input on L3 and level on L3), is as follows.
Table 20: Level two programming example
1.
Press the key [Set] and hold it down (approx. 3 s)
2.
Release the [Set] key when L1 LED starts flashing
3.
Press the key [Set] and hold it down during step 4 and 5
4.
Wait approx. 3 seconds, after which the LED L3 representing the current level of the "Motor Force"
will light up
5.
Press the [
] key twice to move the LED which is lit on to LED L2 which represents the new
"Motor Force" value
6.
Release the key [Set]
7.
Press the [
] key twice to move the flashing LED to LED L3
8.
Press the key [Set] and hold it down during step 9 and 10
9.
Wait approx. 3 seconds, after which the LED L2 representing the current level of the "Pause Time"
will light up
10.
Press the [
] key once to move the LED which is lit on to LED L3 which represents
the new "Pause Time" value
11.
Release the key [Set]
12.
Wait 10 seconds before leaving the program to allow the maximum time to lapse.
7.3) Adding or Removing Devices
Devices can be added to or removed from the SPIN automation sys-
tem at any time. In particular, various devices types can be connect-
ed to the "STOP" input as explained in paragraph "7.3.1 STOP
Input".
7.3.1) STOP Input
STOP is the input that causes the immediate interruption of the
manoeuvre (with a short reverse run). Devices with output featuring
normally open "NO" contacts and devices with normally closed
"NC" contacts, as well as devices with 8,2KΩ constant resistance
output, like sensitive edges, can be connected to this input.
During the recognition stage the control unit recognizes the type of
device connected to the STOP input (see paragraph "4.2 Recogni-
tion of the door opening and closing positions"); subsequently it
commands a STOP whenever a change occurs in the recognized
status.
Multiple devices, even of different type, can be connected to the
STOP input if suitable arrangements are made.
• Any number of NO devices can be connected to each other in par-
allel.
• Any number of NC devices can be connected to each other in
series.
• More devices with 8.2KΩ constant resistance can be connected
in "cascade" with a single 8.2KΩ termination resistance
• The NO and NC combination can be obtained by placing the two
contacts in parallel, and placing in series to the NC contact an
8.2KΩ resistance (therefore, the combination of 3 devices is also
possible: NO, NC and 8,2KΩ).
18
!
if the STOP input is used to connect devices with safe-
ty functions, only the devices with 8,2KΩ constant resis-
tance output guarantee the fail-safe category 3 according
to EN standard 954-1.
Example
3s
SET
L1
SET
SET
L3
3s
L2
SET
L3
SET
L2
3s
L3
SET
10s