Inversion of the output signal

By means of the lower two-pole jumper on the left-hand side above the output
terminals, the output signal can be issued inverted or not inverted.
Jumper open:
not inverted (solar pump)
Jumper connected: inverted (heating pump)
Input
Heating
100 %
0%
2.4

Overrun function

By means of the upper two-pole jumper the overrun function can be activated or
deactivated.
The overrun function can be used to reduce the number of switching processes
for high-efficiency pump. Power supply for the pump will remain switched on for
another 30 minutes after the input signal has signalled a switch-off.
Jumper open:
Overrun function on
Jumper connected: Overrun function off
2.5
Solar
PWM /
0-10 V
100%
output
2.6
3
If the device does not work perfectly, please check the following items:
If the device does not switch on when the power supply is connected, please check
the fuse. The device is protected by a T1A fuse, which can be replaced after having
removed the housing and the cover. A spare fuse is enclosed on the backside of
the cover.

Application example

Overrun Off
PWM 2
1
2
3
R In
10V
Input signal: 230 V control
signal from the controller
(On / Off, burst / wave
Controller
packet, phase cutting)

LED flashing codes

Flashing code
Description
Green:
Output on standby
Green flashing:
Output active

Tips for fault diagnostics