12
1.2. Technical data
Supply voltage
Power consumption
Sensor input
Adjustment setpoint value
temperature
Internal temperature limit (fix
adjusted)
Additional functions,
adjustable via internal DIP-
switch
Display operating status and
fault signal
Running time actuator
Torque actuator
Position indicator
Manual emergency operation
Protection class
Protection degree
Mode of operation
Insulation class
Ambient temperature
Installation position
Housing
Housing colour
Dimensions
Weight
Conformity
Operating and commissioning manual - EN
230 V AC 50 Hz, fix connection via two-core power cord with standardised
european plug, cord length 2 m
3,5 VA
NTC- temperature sensor, 8,2 kΩ at + 25 °C,
fix connected immersion sensor,
cord length 1 m, immersion sleeve Ø6 mm x 43 mm
+ 20 °C to + 80 °C
Minimum temperature limit: + 60 °C or + 70 °C
Maximum temperature limit: + 55 °C
1: Running direction
2: Minimum temperature limit
3: Maximum temperature limit
4: Mixer blocking protection
Via LED´s – red (I) and green (II)
135 s at a rotation angle of 90 °
Max. 10 Nm
Bicoloured scale, selectable by turning over:
Flow right (VR) and flow left (VL)
Via adjustment knob after displacing the gear
II
IP 40 according to DIN EN 60529 (VDE 0470-1)
Type 1 Y (according to DIN EN 60730-1)
2
0 °C to + 50 °C
Variable
Plastics, PC (polycarbonate), fiber-glass reinforced
Black
93 mm x 82 mm x 93 mm
0,47 kg
The fixed-value controller complies with the requirements of the Guidelines
on Electromagnetic Conformity (2004/108/EG), the Low Voltage Directive
(2006/95/EG), the harmonized standards DIN EN 60730-1 and DIN EN
60730-2-9 and carries the CE mark.