Technical Characteristics; Connection Terminals - Comelit 9I8O6A Manual Tecnico

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 8
ART. 20046605 - SIMPLEHOME MODULE WITH 9 OPTICALLY COUPLED INPUTS
AND 8 X 6A RELAY OUTPUTS ON DIN RAIL (9I8O6A)
Module on bus has 8 inputs + 1 scenario input, as well as 8 relay outputs with NO contact with capable of controlling resistive electrical
loads up to 6A. The outputs on the device are not suitable for controlling particularly heavy loads or halogen and fl uorescent lamps.
When controlling these loads, a support contactor must be used at each output.
Power supply voltage
Absorption
Inputs
Outputs
Max. input cable length
Protection
Indications
Lack and restoring of
power supply
Terminals
Positioning
Applicable standards
Approvals
Operating temperature
Storage temperature
Relative air humidity
Weight
Dimensions
green (bus)
red (+)
blue (-)
4

TECHNICAL CHARACTERISTICS

24 Vdc ± 5%
min. 8 mA, max. 167 mA
8+1, optically coupled digital type
8 relay 230 Vac, resistive 6A (cos ϕ = 1)
25 m
against reverse polarity
1 bus status indicator LED: when fl ashing, indicates data transmission via bus, when lit
steadily indicates lack of power supply negative or incorrect device connection
9 input status indicator LEDs
8 output status indicator LEDs
Output status memory
removable for BUS connection
On a DIN rail on a dedicated control panel or in junction boxes *
electromagnetic compatibility: EN 50081-1 (interference emission)
and EN50082-2 (resistance to interference)
CE
0° to 50°C
-10° to +70°C
5 to 95% with no condensation
180 g (not including packaging)
71x90x58 mm (4 DIN modules)
* With access allowed only for support or servicing by qualifi ed personnel
Term.
Function
-
BUS power supply negative
BUS power supply +24 Vdc
+
D
BUS data line
V+
+24 Vdc support
I8
Input 8
I7
Input 7
Input 6
I6
I5
Input 5
I4
Input 4
I3
Input 3
Input 2
I2
I1
Input 1
When connecting a power contactor to the outputs, an anti-interference fi lter must be
fi tted to the contactor coil. (e.g. DETAS art. 901192).
N.B. The module must be programmed vis the BUS line, using the SimpleHome/RS232
interface (20022611) and the SimpleProg programming software.
Specifi cations are subject to change without notice.

CONNECTION TERMINALS

Term.
O1
O2
O3
O4
C1
O5
O6
O7
O8
C2
V+
IS
Function
Output 1 – NO contact
Output 2 – NO contact
Output 3 – NO contact
Output 4 – NO contact
Output common 1-2-3-4
Output 5 – NO contact
Output 6 – NO contact
Output 7 – NO contact
Output 8 – NO contact
Output common 5-6-7-8
+24 Vdc support
Multiple command (scenario)

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

20046605

Tabla de contenido