Warning
• This Comelit product was designed for use in the creation of security and home automation systems in residential, commercial or industrial settings
and in public buildings or buildings used by the public.
• All activities connected to the installation of Comelit products must be carried out by qualified technical personnel, with careful observation of the
indications provided in the manuals / instruction sheets supplied with those products.
• Use wires with a cross-section suited to the distances involved, observing the instructions provided in the system manual.
• We advise against running the system wires through the same duct as the power cables (230V or higher).
• Cut off the power supply before carrying out any maintenance procedures.
• To ensure Comelit products are used safely: carefully observe the indications provided in the manuals / instruction sheets and make sure the system
created using Comelit products has not been tampered with / damaged.
• Comelit products do not require maintenance aside from routine cleaning, which should be carried out in accordance with the indications provided in
the manuals / instruction sheets. Any repair work must be carried out: for the products themselves, exclusively by Comelit Group S.p.A., for systems,
by qualified technical personnel.
• Comelit Group S.p.A. does not assume any responsibility for: any usage other than the intended use; non-observance of the indications and warnings
contained in this manual / instruction sheet. Comelit Group S.p.A. nonetheless reserves the right to change the information provided in this manual /
instruction sheet at any time and without prior notice.
ART. 20004820
Module 20004820 is equipped with a 0-10V / 4-20m analogue input, a 0-10V output and a digital input. The
analogue input may be used for connection of analogue sensors, such as light sensors for indoor/outdoor use,
level sensors, wind sensors, etc. The 0-10V output can be used for connection of LED lights, fluorescent lights
or other devices equipped with a 0-10V input. The module is equipped with a digital input, freely programmable
via the programming software, for the connection of normal pushbuttons and switches or for the connection of
sensors with voltage-free contacts (e.g. presence sensors).
TECHNICAL CHARACTERISTICS
Power supply voltage
Consumption (max)
Maximum output current
0-10V
Type of analogue input
Maximum input cable length 10 m (0-10V analogue input)
Operating temperature (°C)
Operating humidity (%)
Indicators
Installation
IP Protection rating
Dimensions (mm)
Weight (g)
PROGRAMMING
SimpleProg software is required to program Comelit home automation devices; this software can be
downloaded from the website pro.comelitgroup.com. Programming must be carried out by connecting the
device to the BUS and sending the programming over this.
ADDRESSING
The address of the module on the Comelit home automation BUS must be set using the DIP-switches on the
module itself, see table on page 8.
• If the DIP-switches are altered, the power supply must be cut off and reactivated for the new address
to be set on the module.
• The module address cannot be changed via SimpleProg.
Comelit home automation BUS 24 Vdc
30 mA
10mA short circuit protection
to be set via SimpleProg software
20 m (4-20 mA analogue input)
25 m (Digital input)
-5 +45
5-95
• Flashing yellow LED: data
transmission on home automation BUS.
• Steady yellow LED: power supply
negative absent or incorrect connection
of device.
• Red LED: possible collision of
messages on home automation BUS.
On DIN rail or in flush-mounted boxes
20
50 x 50 x 21
30
TERMINAL BLOCK
Home automation BUS
D
data line
+
Power supply positive
-
Power supply negative
Analogue input 0-10V /
AI
4-20 mA
Common for analogue
GND
inputs and outputs
AO
Analogue output 0-10V
Reference +24 Vdc for
V+
digital input
I1
Digital input
3