Technical Characteristics; Connection Terminals - Comelit SimpleHome 2 Manual Tecnico

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 8
ART. 20046810 - SIMPLEHOME MODULE WITH 2 ANALOGUE INPUTS
AND 2 ANALOGUE OUTPUTS ON DIN RAIL (2I2O)
Interface on DIN rail for SimpleHome system, with two inputs and two 0-10 V analogue outputs. Allows interfacing between the
automation system and analogue inputs, such as light sensors or voltage/current transformers, as well as the management of electronic
adjustment devices such as lighting ballasts or dimmers. It is not suitable for the connection of the temperature sensor with 0-10 V
output (20046708).
Power supply voltage
Absorption
Inputs
Maximum input cable length
Outputs
Protection
Indications
Terminals
Positioning
Lack and restoring of power supply
Applicable standards
Approvals
Operating temperature
Storage temperature
Relative air humidity
Weight
Dimensions
green (bus)
red (+)
blue (-)
DIMMER OR BALLAST
ELECTRONIC
4

TECHNICAL CHARACTERISTICS

24 Vdc ± 5%
min. 5 mA, max. 30 mA
2 analogue, 0-10 V
5 m
2 analogue, 0-10 V with max. current 100 mA
against reverse polarity
1 bus status indicator LED: when fl ashing, indicates data transmission via bus,
when lit steadily indicates lack of power supply negative or incorrect connection
of the device
removable
On a DIN rail on a dedicated control panel or in junction boxes*
output status memory
electromagnetic compatibility: EN 50081-1 (interference emission)
and EN50082-2 (resistance to interference)
CE
0° to 50°C
-10° to +70°C
5 to 95% with no condensation
130 g (not including packaging)
53x90x58 mm (3 DIN modules)
* With access allowed only for support or servicing by qualifi ed personnel
Term.
-
+
D
IA2
V-
+10
IA1
V-
+10
OA1
V-
OA2
V-
N.B. The module must be programmed vis the BUS line, using the SimpleHome/
RS232 interface (20022611) and the SimpleProg programming software.
Specifi cations are subject to change without notice.

CONNECTION TERMINALS

Function
BUS power supply negative
BUS power supply +24 Vdc
BUS data line
Input 2 (0-10 V)
GND
+10 Vdc support at input 2
Input 1 (0-10 V)
GND
+10 Vdc support at input 1
Output 1 (0-10 V)
Output 1 support negative
Output 2 (0-10 V)
Output 2 support negative

Publicidad

Tabla de contenido
loading