Ferroli BlueHelix HiTech RRT C Instrucciones De Uso, Instalación Y Mantenimiento página 330

Ocultar thumbs Ver también para BlueHelix HiTech RRT C:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Index Description
Summer/Winter mode
b05
Variable input contact operation
b06
selection
Relay card LC32 selection
b07
Hours without DHW draw-off
b08
Fault 20 status selection
b09
Not implemented
b10
Flowmeter timing
b11
Not implemented
b12
Not implemented
b13
DHW factor
b14
Flowmeter type selection
b15
Not implemented
b16
Not implemented
b17
DHW mode activation flow rate
b18
DHW mode deactivation flow
b19
rate
Flue material selection
b20
Not implemented
b21
Not implemented
b22
Standard flue shutdown maxi-
b23
mum temperature
PVC flue shutdown maximum
b24
temperature
CPVC flue shutdown maximum
b25
temperature
Not implemented
b26
Calibration procedure [AUTO
b27
SETUP]
Not implemented
b28
330
BlueHelix HiTech RRT C
Range
0 = WINTER - SUMMER - OFF
1 = WINTER - OFF
0 = Flowmeter exclusion
1 = System thermostat
2 = Second room therm.
3 = Warning/Alert
4 = Safety thermostat
0 = External gas valve
1 = Alarm
2 = System filling solenoid valve
3 = Solar 3-way valve
4 = Second heating pump
5 = Alarm2
6 = Burner lit
7 = Frost protection On
0-24 hours (time for temporary deactivation of
comfort mode without draw-off)
0 = Deactivated
1 = Enabled (only for versions with pressure trans-
ducer)
--
0 = Deactivated
1-10 = seconds
--
--
0 - 1
1 = Flow. (450 imp/l)
2 = Flow. (700 imp/l)
3 = Flow. (190 imp/l)
--
--
0-100 l/min/10
0-100 l/min/10
0 = Standard
1 = PVC
2 = CPVC
--
--
60-110°C
60-110°C
60-110°C
--
5 = Calibration procedure [AUTO SETUP] enabled
All other values = Calibration procedure [AUTO
SETUP] disabled
(See "Calibration procedure [AUTO SETUP]"
on page 328)
--
cod. 3541V300 - Rev. 00 - 02/2021
Default
0 = Enabled
2
0
24
0
--
0
--
--
0
3
--
--
25
20
0
--
--
105
93
98
--
0
--
EN

Hide quick links:

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido