INSTALLATION INSTRUCTIONS
C-TR-A-BT LED Series
CAUTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions
should always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1.
DANGER- Risk of shock- Disconnect power before
installation.
DANGER – Risque de choc – Couper l'alimentation
avant l'installation.
2.
This luminaire must be installed in accordance with the
NEC or your local electrical code. If you are not familiar
with these codes and requirements, consult a qualified
electrician.
Ce produit doit être installé conformément à NEC ou
votre code électrique local. Si vous n'êtes pas familier
avec ces codes et ces exigences, veuillez contacter un
électricien qualifié.
3.
Suitable for damp locations.
Convient aux emplacements humides.
SAVE THESE INSTRUCTIONS FOR
FUTURE REFERENCE
http://lighting.cree.com/warranty
Document:
LPN00606X0001A0_A
Created By:
TMT
INSTALLATION
1.
Locate desired fixture location in ceiling grid.
2.
Remove existing ceiling panel at chosen location. Remove
adjacent ceiling panel to allow for wiring access from above.
3.
Place fixture into T-bar ceiling grid. Bend clips on sides of fixture
to engage with T-bar support grid. See Figure 1. If necessary, use
side cutters to adjust each tab to height of T-grid.
4.
Secure fixture to grid in compliance with state and local codes.
5.
Remove screw on driver wiring chamber, slide cover to side, and
remove cover. Set screw and cover aside to be reinstalled later.
6.
Remove appropriate 1/2" knockout(s) to allow for entry of supply
wiring into wiring chamber.
7.
Make wiring connections per the Electrical Connections section.
8.
Reattach wiring chamber cover with screw that was removed in
Step 5 above.
9.
Replace adjacent ceiling panel that was removed in Step 2 above.
FIGURE 1
ELECTRICAL CONNECTIONS
Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
DIMMING
1. Grey (-) and violet (+) leads are for 0-10V dimming
systems. Cap off if not used.
NOTE: For dimming connections, use Class 1 wiring
methods only.
|
866.924.3645
Date:
07-18-2018

Publicidad

loading

Resumen de contenidos para Cree C-Lite C-TR-A-BT LED Serie

  • Página 1 Tuck all wires carefully into wiring chamber ensuring that no wires are pinched. DIMMING 1. Grey (-) and violet (+) leads are for 0-10V dimming systems. Cap off if not used. NOTE: For dimming connections, use Class 1 wiring methods only. http://lighting.cree.com/warranty 866.924.3645...
  • Página 2 Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. CAN ICES-005 (A)/NMB-005 (A) http://lighting.cree.com/warranty 866.924.3645...
  • Página 3 1. Los cables gris (-) y morado (+) son para los sistemas de atenuación de 0-10 V. Aíslelos si no se van a utilizar. NOTA: Para las conexiones del sistema de atenuación, use únicamente métodos de cableado de clase 1. http://lighting.cree.com/warranty 866-924-3645...
  • Página 4 Es probable que el uso de este equipo en un área residencial cause interferencias perjudiciales, en cuyo caso el usuario deberá corregir dicha interferencia por su propia cuenta. CAN ICES-005 (A)/NMB-005 (A) http://lighting.cree.com/warranty 866-924-3645...
  • Página 5: Mesures De Sécurité Importantes

    1. Les fils gris (-) et violet (+) sont pour les systèmes de gradation de 0 à 10 V. Protégez d’un capuchon si non utilisé. REMARQUE : Pour les branchements de gradation, utilisez seulement les méthodes de câblage de la classe 1. http://lighting.cree.com/warranty 866-924-3645...
  • Página 6 L’utilisation de cet équipement dans une zone résidentielle va sans doute causer une interférence nuisible où il sera requis que l’utilisateur corrige l’interférence à ses propres frais. CAN ICES-005 (A)/NMB-005 (A) http://lighting.cree.com/warranty 866-924-3645...