Please note with branch lines:
–
the total maximum length of the AS-Interface bus:
100 m (without repeater/extender).
–
the cable length of the load voltage connection
(depends on the ccurrent consumption of the valve
terminal and the fluctuations in the load voltage).
–
seal unused cable ends with the Fest cable cap ASI-KK-
FK or the cable sleeve ASI-KT-FK. In this way you will
avoid leakage currents and comply with protection
class IP65.
1
Pin 2: AS-Interface +
(brown)
Pin 1: AS-Interface -
2
(light blue)
Pin 2: + 24 V
3
4
Pin 1: 0 V
Recommendation: For connecting the valve terminal use
the Festo cable sockets ASI-SD-FK. You will then comply
with protection class IP65.
Proceed as follows:
1. Connect the cable in accordance with separate quick
reference guide.
2. Make sure that the AS-Interface cable is free of tension.
3. Place the cable socket in position and screw it tight.