This instruction sheet provides you with the information required to safely own
and operate your product. Retain these instructions for future reference.
The product you have purchased is of the highest quality workmanship and
material, and has been engineered to give you long and reliable service. This
product has been carefully tested, inspected, and packaged to ensure safe
delivery and operation. Please examine your item(s) carefully to ensure that no
damage occurred during shipment. If damage has occurred, please contact the
place of purchase. They will assist you in replacement or repair, if required.
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO
INSTALL, OPERATE, OR SERVICE YOUR PRODUCT. KNOW THE PRODUCT'S
APPLICATION, LIMITATIONS, AND POTENTIAL HAZARDS. PROTECT
YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION.
FAILURE TO COMPLY WITH THESE INSTRUCTIONS COULD RESULT IN
PERSONAL INJURY AND/OR PROPERTY DAMAGE!
DECLARATION OF CONFORMITY
We, Franklin Electric, declare that our pumps TPR, TPT & TPS with pump type
and serial number as shown on the nameplate are constructed in accordance
with Directives 2006/95/EC and 89/336/EEC and assume full responsibility for
conformity with the standards laid down therein.
DESCRIPTION
Your Little Giant peristaltic condensate pump is designed as a fully automatic
condensate removal system for the water dripping off an air conditioner
evaporator coil. The pump is not for contiuous use applications. The pump you
have purchased is a small but powerful drain pump for the positive displacement
of condensate from fan coils and air conditioners. The design of this pump allows
the air handler to be located away from gravity water drains since the condensate
can be pumped to a common drain a distance away. The peristaltic pump is
designed to remove condensation from fan coil, wall-mount, ceiling and cassette
air conditioning equipment.
SAFETY GUIDELINES
SHUT OFF ELECTRICAL POWER AT FUSE BOX BEFORE ATTEMPTING TO
SERVICE, DISCONNECT, CONNECT OR REMOVE ANY COMPONENT!
1. This pump is not to be used to pump flammable or explosive fluids such
as gasoline, fuel oil, kerosene, etc. Do not use this pump in explosive
atmospheres.
2. Do not handle pump with wet hands or when standing on a wet, damp
surface or when standing in water.
3. In any installation where property damage and/or personal injury might result
from an inoperative or leaking pump due to power outages, discharge line
blockage, or any other reason, a backup system(s) and/or alarm should be
used.
4. Support pump and piping when assembling and when installed. Failure to
do so may cause piping to break, pump to fail, motor bearing failures, etc; or
may cause the pump to malfunction.
5. Place pump in an area where there is no danger of ingress of water.
SPECIFICATIONS
Maximum suction head:
Maximum delivery head:
Maximum ambient temperature: 50°C (122°)
PRE-INSTALLATION
1. Check the pump label for proper voltage and frequency required. Do not
connect to voltage and frequency other than that shown.
2. It is recommended to use ¼" I.D. or 6 mm I.D. tubing for both the inlet and
outlet. Inlet tubing is connected to the inlet fitting identified by an upward
arrow. Outlet or discharge tubing is connected to the outlet fitting identified
by a downward arrow.
3. Make sure the transparent cover is closed before operating.
INSTALLATION
Pump Mounting Installation:
The pump can be mounted adjacent, below or above (but not more than 2m
above) the condensate water source.
For best results, mount the pump with the hose connections facing down as
shown in Figure 1B.
MODELS • MODÈLES •
MODELOS
TPS • TPT • TPR
ENGLISH
2m (6.5 ft)
14m (49 ft)
A
B
The pump may also be positioned on any side, but not placed rotor downward
(Figure 1C) or upward (Figure 1A). Connect 6.0mm or 1/4" tubing (not provided)
to the pump intake indicated by the arrow pointing upward on the transparent
cover. Position the other end of the intake tube in the drip tray drain hose and
seal it accordingly or place the intake tube in the drip tray (Figure 2). Be careful
not to twist, kink, or collapse the tubing. Run a length of 6.0mm or ¼" tubing (not
provided) from the discharge of the pump to a gravity drain. Refer to Figure 2 for
maximum vertical and horizontal discharge capabilities.
16 ft (5 m)
max
"Your Solution Innovator"
Red end: room air
6.5 ft (2 m) max
sensor, intake air
Coil
Blue end: cold air
sensor, intake air
Block off unit drain
Internal drain tray
Wall or below ceiling A/C unit
CAUTION: Be certain that there are no sharp bends or kinks in the suction and
discharge tubing. Keep all tubing and cables clear of moving parts in the air
handler. If using Ty-raps to secure tubing, be certain the Ty-rap does not collapse
tubing.
Collection Reservoir Installation (R Series only):
Locate the float reservoir in a suitable position below the bottom level of the drip
tray of the air conditioner. Be certain that the reservoir is within (+/-) 15 degrees
of being level. Optimum performance is achieved when the reservoir is level. If the
reservoir is not mounted properly, the float mechanism may not function properly
and may overflow.
Attach the 13mm (1/2") tube (provided) to the reservoir intake and the drip tray
outlet or drain hose. Be certain to support the reservoir when attaching tubing
and make sure the tubing is not twisted, kinked or collapsed when reservoir is
in place. Connect the long 4 x 6 mm (5/32") tubing (provided)to the discharge
of the reservoir marked "PUMP". Connect the other end of the 4 x 6 mm (5/32")
tubing to the provided 4 x 6 mm adapter. Use a short piece of 6 mm or ¼" tubing
(not provided) to connect the 4 x 6 mm adapter to the pump inlet fitting identified
by an upward arrow. Connect the short 4 x 6 mm (5/32") tubing (provided) to
the outlet of the reservoir marked "VENT". The free end of the tubing must be
directed upward above the drip tray to prevent overflow. Be certain the tubing is
not twisted, kinked or collapsed when installed.
ELECTRICAL CONNECTIONS
SHUT OFF ELECTRICAL POWER AT FUSE BOX BEFORE MAKING ANY
CONNECTIONS. ALL WIRING MUST COMPLY WITH LOCAL CODES. CHECK
THE PUMP LABEL FOR PROPER VOLTAGE REQUIRED. DO NOT CONNECT TO
VOLTAGE OTHER THAN THAT SHOWN.
TPS Series (compressor or cooling signal) - Connect the brown wire to the main
phase (line), the blue wire to the neutral phase (common). The pump must not
be connected to a switched line. Electricity should always be provided on this
line. Connect the orange wire to the compressor or cooling signal (Figure 3).
When the compressor engages, a 230V supply voltage will be sent to start the
pump. When the compressor stops operating, the pump will not stop. The pump
is programmed to continue operating for another 5 minutes to collect any residual
condensate before stopping.
NOTE: The compressor or cooling signal neutral phase (common) needs to be
the same neutral phase (common) that is used to supply power to the controller.
TPT Series (temperature signal) FOR PROPER PUMP OPERATION, PLEASE
FOLLOW THESE INSTRUCTIONS: Connect the brown wire to the main phase
(line) and the blue wire to the neutral phase (common) (Figure 2). Make sure
power is off when connecting the temperature sensor to the pump. Connect the
sensor cable to the pump by connecting the 4-prong plug to the corresponding
C
FIGURE 1
TPT
98 ft (30 m)
max
Lt. blue
Brown
To pump
Ceiling
Internal
drain tray
Alternative position for inlet tube
FIGURE 2
D
46 ft (14 m)
max
Inlet tube fixed
inside tray
outlet with
sealant
1

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Franklin Electric Little Giant TPS

  • Página 1 Brown "Your Solution Innovator" DECLARATION OF CONFORMITY We, Franklin Electric, declare that our pumps TPR, TPT & TPS with pump type and serial number as shown on the nameplate are constructed in accordance To pump with Directives 2006/95/EC and 89/336/EEC and assume full responsibility for Red end: room air 6.5 ft (2 m) max...
  • Página 2: Declaration De Conformite

    RESPECT DE CES DIRECTIVES PEUT ENTRAÎNER DES BLESSURES ET/OU DES DOMMAGES MATÉRIELS! "Your Solution Innovator" DECLARATION DE CONFORMITE Nous, Franklin Electric déclarons que les pompes TPR, TPT, TPS modèle et numero de série marqués sur la plaque signalétique sont conformes aux Directives 2006/95/EC, 89/336/EEC. FIGURE 5 DESCRIPTION Votre pompe péristaltique à...
  • Página 3: Directives De Sécurité

    La conception de cette pompe permet que la section de traitement d’air soit éloignée des purges d’eau, puisque le condensat peut être pompé vers un drain commun situé à une certaine distance. La pompe péristaltique est conçue pour enlever la condensation d’un montage mural, de l’équipement de plafond et de cassette d’un conditionneur d’air et d’un serpentin.
  • Página 4: Declaracion De Conformidad

    DECLARACION DE CONFORMIDAD de la pompe. Appuyer sur l’interrupteur de vérification pour déterminer si la En Franklin Electric declaramos bajo nuestra exclusiva responsabilidad que las pompe fonctionne correctement. bombas TPR, TPT, y TPS modelo y numero de serie marcados en la placa de caracteristicas son conformes a las disposiciones de las Directivas 2006/95/EC, S’ASSURER...
  • Página 5: Especificaciones

    2. No maneje la bomba con las manos mojadas o cuando se encuentre parado Coloque el depósito con flotante en una posición adecuada debajo del nivel sobre una superficie mojada, húmeda o cubierta con agua. inferior de la bandeja de goteo de la unidad de aire acondicionado. Asegúrese de que el depósito esté...
  • Página 6: Mantenimiento

    LIGERO AZUL MARRÓN LA CONFIGURACIÓN DEL CABLEADO "Your Solution Innovator" DE LA BOMBA VARIARÁ SEGÚN EL MODELO ADQUIRIDO. 599270 T-RPC ENSAMBLADO DE TUBO DE REPUESTO FIGURA 4 Serie TPR (conexión de reboso/alarma) - Conecte los cables como se describe a continuación para obtener la respuesta deseada: NO SE MUESTRAN LAS PIEZAS DE REPUESTO C y NC - Cuando el nivel de agua sube, se abre el circuito que apaga el compresor y evita que ésta se rebose, ya que se conecta el cable gris con el...
  • Página 7: Garantie Limitée

    LIMITED WARRANTY D’APTITUDE PARTICULIÈRE, POUVANT S’APPLIQUER À UNE POMPE LITTLE GIANT. DE PLUS, ELLE NE S’APPLIQUE QUE DURANT LA PÉRIODE DE Your Little Giant product is guaranteed to be in perfect condition when it leaves our COUVERTURE PRÉCISÉE CI-DEVANT. Factory. It is warranted against defective materials and workmanship for a period of 24 months from date of purchase by the user.
  • Página 8 ..... . .1-888-572-9933 Para la ayuda técnica, por favor póngase en contacto ..1-888-956-0000 www.LittleGiantPump.com CustomerService-WTS@fele.com Form 998554 - 03/26/2010 © 2009 Franklin Electric Co., Inc. Little Giant® is a registered trademark of Franklin Electric Co., Inc.

Este manual también es adecuado para:

Little giant tptLittle giant tpr

Tabla de contenido