Enter the reversing impulse (**) for overload/underload "Reverse Impulse"
Using the buttons, set the desired value in 10 ms steps
or
from 0 to 60 s (Default: 0 s)
(**) Default "only after overload/underload detection".
Another operating mode can only be set via ELR-CONF software.
Press button:
Confirm data entered.
Select:
or
"SAVE":
"Default":
"EXIT":
Press button:
Confirm selection.
Special function of the keys in edit mode
In edit mode, pressing the
or
accelerates the up/down counting speed.
In edit mode, briefly hitting the edit key
+
button
or
accelerates the up/down counting speed.
By releasing the key and then briefly pressing it again, it is possible
+
to carry out fine adjustments.
4.3. Monitor Mode (display)
Press buttons simultaneously (< 3 s), then
+
Select:
or
U, I, P, S, Q, cos phi, f, operating hours counter (OPtime) or
operating cycles meter (OPCYCL) or
EXIT (You exit the monitor mode).
Press button.
Confirm selection and display.
With I, U:
or
selection for L1, L2 or L3.
With operating cycles counter (OPCYCL):
or
Select between Reverse and Forward.
Press button.
Continue in monitor mode.
20
5. Messages on the Display
=
LED "Message/Error"
(IND.) lights up
Display flashing -
No load connected!
Display flashing -
Write data into
device!
Display flashing -
Read out data from
device!
Display flashing -
Reset threshold
reverse LOW
fallen below!
Display flashing -
Reset threshold
forward LOW
fallen below!
Display flashing -
Reset threshold
reverse HIGH
exceeded!
Display flashing -
Reset threshold
forward HIGH
exceeded!
22
Set values are saved.
Returns to default values.
You exit enter mode.
or
key for longer than five seconds
in addition to
Display flashing -
Message threshold
reverse LOW
fallen below-
Depending on the
configuration, you may
have to reset the
message manually !
Display flashing -
Message threshold
forward LOW
fallen below -
Depending on the
configuration, you may
have to reset the
message manually !
Display flashing -
Message threshold
reverse HIGH
exceeded -
Depending on the
configuration, you may
have to reset the
message manually !
Display flashing -
Message threshold
forward HIGH
exceeded -
Depending on the
configuration, you may
have to reset the
message manually !

4.4. Extended Mode

Caution: Connected equipment can be switched on directly!
Press buttons simultaneously for approx. 3 secs., then
+
Select:
or
"PnEt.REG":Mains regeneration time
"rES.LOG" Reset logging system
"rES.tIME" Reset operating hours counter
"rES.COUNt"Reset operating cycles counter
"Hand"
"EXIT"
Press button.
Confirm selection.
"PnEt.REG."
Enter mains regeneration time:
Using the buttons, set the desired value in 10 ms steps
or
from 0 to 60 s (Default: 3000 ms)
Press button:
Confirm data entered and return to selection.
"rES..."
Reset memory or counter:
Press button:
Confirm data entered and return to selection.
"Hand"
Manual reverse/forward running:
Caution: Connected equipment is switched on directly!
Press button: Inching mode forward running
Press buttons simultaneously:
+
Continuous operation, manual forward running.
The setting engages.
or
or
Press button: Inching mode reverse running
Press buttons simultaneously:
+
Continuous operation, manual reverse running.
The setting engages.
or
or
Press button:
Confirm data entered and return to selection.
Display flashing -
24 V supply
switched on before
400 V/500 V supply!
Display with
permanent display -
failure of 400 V/500 V
supply during
operation!
Phase shift in the
400 V/500 V supply!
Display flashing -
Wire break in
motor line T1!
Display flashing -
Wire break in
motor line T2!
Display flashing -
Wire break in
motor line T3!
Manual reverse, manual forward running
You exit the extended mode.
Press button: Stops continuous operation.
Press button: Stops continuous operation.
Display flashing -
Simultaneous
triggering of "reverse"
and "forward"!
Display flashing -
Malfunction in
uninterrupted
data logging -
For reset please use
"Extended mode"
(select: "rES.LOG")!
Device error -
Interrupt the
supply voltage to
clear the message!
Display flashing -
Error in configuration!
Rewrite the
configuration into the
device.