6. Technical data
ELR W...
Order No.
Input data
Operating voltage U
B
Nominal current at U
, (without
N
feed-back)
For input R (forward) and L (reverse):
Control voltage
Nominal current
Switching threshold U
in
Switching threshold U
off
Operating voltage display
Direction of rotation indicator:
Phase sequence forward / reverse
Error display
Input circuit
Output data
Conductor voltage max.
Max. switching voltage
L1/T1
L2/T2
L3/T3
Mains frequency
Load current at 20 °C (see derating)
Minimum capacity
Minimum load current per phase
Leakage current in off state
Residual current at I
N
Surge current Tvj = 45 °C
Max. load value Tvj = 45 °C
Peak reverse voltage
Surge voltage suppression
Output circuit
Acknowledge outputs
Signaling contacts
Default:
(O1 - O4 can be freely
parameterized via
ELR-CONF software)
Operating voltage at "1" signal
Nominal current
24
6. Technical data
ELR W...
General data
Insulation voltage
Operating and control voltage/
output
Output / PE
Ambient temperature range
Nominal operating mode
Standards/regulations
Insulation distances
Safe isolation: Input/Output
Shock test
Vibration
Power station requirement
Degree of protection
Installation position
Assembly
Housing:
Material
Dimensions (W/H/D)
Connection data
(conductor cross section)
• Screw terminal blocks (solid/strand.)
• COMBICON plug connector
Weight
26
...3/9-400 MM
...3/9-500 MM
...3/2-500 MM
29 63 51 4
29 63 54 3
29 82 62 1
24 V DC ± 20 %
80 mA
24 V DC ± 20 %
5 mA
7 mA
7 mA
U > 0.8 x U
N
U < 0.4 x U
N
LED green
LED yellow / LED yellow
LED red
Polarity protection, surge voltage protection,
input capacitor
Load side
110-433 V AC
110-550 V AC
110-550 V AC
440 V AC
550 V AC
550 V AC
440 V AC
550 V AC
550 V AC
440 V AC
550 V AC
550 V AC
50/60 Hz
3 x 8 A
3 x 8 A
3 x 1.8 A
100 W
150 mA
3 x 4 mA
3 x 7 mA
3 x 7 mA
1.4 V
360 A (t = 10 ms)
2
645 A
s
1000 V
1500 V
1500 V
750 V
880 V
880 V
RCV circuit
"O1" = Message, message threshold
"O2" = Message, switching threshold
"O3" = Forward running
"O4" = Reverse running
U
– 1 V
B
max. 50 mA
...3/9-400 MM
...3/9-500 MM
...3/2-500 MM
2.5 kV
, 50 Hz, 1 min.
eff
2.5 kV
, 50 Hz, 1 min.
eff
0.5 kV
, 50 Hz, 1 min.
eff
-20 °C to +60 °C
100 % operating factor
DIN EN 50178 /VDE 0160:1998-04
VDE 106 Part 101
DIN EN 60068-2-27 / IEC 68-2-27
DIN EN 60068-2-6 / IEC 68-2-6
DWR 1300 / ZXX01/DD/7080.8d
IP20
Vertical (horizontal DIN rail)
In rows with spacing ≥ 20 mm
Polycarbonate PC, green
(62 / 94 / 122) mm
2
0.2-6 / 0.2-4 mm
(AWG 24-10)
approx. 740 g
6. Technical data
ELR W...
Measuring technology and display
• Current measurement
Measuring range
Display
Precision
Resolution
• Voltage measurement/phase-to-neutral voltage
Measuring range
Display
Precision
Resolution
• Power measurement
Measuring range
Display
Precision
(motor-driven operation, tu 20 °C)
Resolution
Measuring rate / Data logging
Trigger criteria for power setpoints
Switching times
Acknowledge signals "O1", "O2":
Switch-off time overload/underload
Acknowledge signals reverse/
forward:
duty cycle
switch-off time
Reaction time for IND:
(f
= 50 Hz)
mains
Reaction time in normal load
operation
duty cycle
switch-off time
Switch-over frequency
Data interface
Data rate
c
c
c
c
in conformance with EMC guideline 89/336/EEC
and low voltage directive 73/23/EEC
EMC (electromagnetic compatibility)
Immunity to interference in acc. with EN 61000-6-2
• Discharge of static electricity (ESD)
• Electromagnetic HF field:
• Fast transients (Burst):
• Surge voltage capacities (Surge):
• Conducted disturbance
• Mains variations
Noise emission in acc. with EN 61000-6-3
• Emitted radio interference
• Radio interference voltage at mains input
• Harmonics
• Voltage fluctuations
Derating curve for ELR W 3/9...MM
(Load current as a function of the ambient temperature)
10
8
6
4
2
0
0
10
20
30
40
50
Ambient temperature [°C]
...3/9-400 MM
...3/9-500 MM
...3/2-500 MM
current transducer for any conductor current
0.25 - 8 A
0.25 - 8 A
0.1 - 2 A
4-digit
± 2 % of end value, typ. ± 1 %
1 mA
0 - 300 V
0 - 350 V
0 - 350 V
4-digit
± 2 % of end value, typ. ± 0.5 %
0.1 V
-6 kW...+6 kW
-8 kW...+8 kW
-2 kW...+2 kW
Values between ... are not permitted!
-100 W... +100 W -100 W... +100 W -30 W...+30 W
In this range the current may fall below the
minimum current for the semiconductor!
4-digit
± 2 % of end value, typ. ± 1 %
(cos ϕ 0.7,
(cos ϕ 0.7,
(cos ϕ 0.3...0.7,
I = 8 A)
I = 8 A)
I = 1.8 A)
1 W
1 measured value per period
Sliding average over 3 periods
< 65 ms
< 25 ms
< 25 ms
< 70 ms (three periods + switching cycle)
< 35 ms
< 25 ms
< 2.5 Hz
RS-232
max. 4.8 kbit/s
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
EN 55011
EN 55011
EN 61000-3-2
EN 61000-3-3
60
25
27

Publicidad

Tabla de contenido
loading