EN
1 SAFETY
1.1 International Safety Symbols
This symbol, adjacent to another symbol or terminal, indicates the user must refer to the
manual for further information.
This symbol, adjacent to a terminal, indicates that, under normal use, hazardous voltages
may be present.
Double insulation
1.2 Safety Notes
-
Do not exceed the maximum allowable input range of any function.
-
Do not apply voltage to meter when resistance function is selected.
-
Set the function switch OFF when the meter is not in use.
-
Remove the battery if meter is to be stored for longer than 60 days.
1.3 Warnings
-
Set function switch to the appropriate position before measuring.
-
When measuring volts do not switch to current / resistance modes.
-
Do not measure current ton a circuit whose voltage exceeds 600V.
-
When changing ranges always disconnect the test leads from the circuit under test.
-
1.4 Cautions
-
Improper use this meter can cause damage. Shock, injury or death.
-
Always remove the test leads before replacing the battery or fuses.
-
Inspect the condition of the test leads and the meter itself for any damage before operating
the meter. Repair or replace any damage before use.
-
Use great care when making measurements if the voltage is greater than 25VAC rms or 35VDC.
These voltages are considered a shock hazard.
-
Always discharge capacitors and remove power form the device under test before performing
diode, resistance or Continuity tests.
-
Voltage checks on electrical outlets can be difficult and misleading because of the uncertainty
of connection to the recessed electrical contacts. Other means should be used to ensure that
the terminals are not "live".
KPA-01T
CLAMP METER TRMS
26 / 50