Festo VMPA-ASI-EPL-8E8A-Z Serie Manual Del Usuario página 19

Terminal de válvula mpa con interfaz as
Ocultar thumbs Ver también para VMPA-ASI-EPL-8E8A-Z Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 31
Diagnosis / display status LED for AS-Interface
AS-i
Fault 1
Fault 2
on
off
off
off
flashes on
on
flashes Short circuit/overload at input
flashes flashes Additional power supply not applied, undervoltage
on
on
AUX/PWR
on
off
Display status LED for inputs
on
off
Note
The AS-Interface has an integrated watchdog function
which resets the outputs if the bus communication
fails.
Festo VMPA-ASI-EPL-...-8E8A-Z/-CE 1104b English
Significance
AS-Interface voltage present, no fault
AS-Interface voltage not applied
AS-Interface address not set ( = 0)
(possibly valves do not switch), periphery fault
Failure of bus communication
(Watchdog expired)
Significance
Additional supply exists
No additional supply or additional supply failed
1-signal at input/output
0-signal at input/output
19

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Vmpa-asi-epl-8e8a-ce serie

Tabla de contenido