Communication
Power supply
Bus current consumption
Bus cable
Command elements
Actuation elements
Maximum switchover current
Maximum power for load type
Maximum dispersible power
Visualisation elements
Usage environment
Operating temperature
Storage temperature
Relative humidity
Bus connection
Electric connections
Degree of protection
Size
Standard references
Certifications
TECHNICAL DATA
KNX BUS
via KNX BUS, 29V DC SELV
10 mA max
KNX TP1
1 miniature programming key
3 interlocked tilting push-buttons
1 relay with NO/NC potential-free contact
10A (cos =1)
Incandescent lamps (230V AC): 1500W
Halogen lamps (230V AC): 1500W
Loads controlled by electronic transformers: 600VA
Uncompensated fluorescent loads: 400VA
Energy efficient lamps (compact fluorescent): 8x23W
For compensated fluorescent lamps and all other loads
not indicated here, you are advised to use a support relay
1W
1 red programming LED
6 amber/green LEDs for load signalling the status
of the commanded load, or for night-time localisation
Dry, indoor places
-5 ÷ +45°C
-25 ÷ +70°C
Max 93% (non condensative)
2-pin coupling terminal - Ø 1mm
Screw terminals - max. cable section 2.5mm²
IP20
3 Chorus modules
Low Voltage Directive 2006/95/EC
Electromagnetic Compatibility Directive
2004/108/EC
EN50428, EN50090-2-2, EN60669-2-1
KNX