Installation; Supplies Required - Bradley S19-120FM Guia De Instalacion

Ocultar thumbs Ver también para S19-120FM:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation

Installation

Supplies Required:

• Pipe sealant
• Piping to 1" NPT water supply inlet
• Adequate supply pipe supports
• Minimum 4" (102 mm) drain to accommodate 30
gallons (115 liters) per minute discharge for shower
waste
• (2) Ceiling fasteners (holes in cover plate are Ø 1/4")
• Sign-mounting hardware
Step 1: Install drench shower
1. Rough-in the necessary ceiling cutouts as shown.
2. Connect the drench shower piping as shown on
page 4.
• Apply pipe sealant to all male-threaded pipe
joints.
• The bottom edge of the showerhead should be
7'-0" (2134 mm) from the floor.
3. Assemble the showerhead components (Item 6)
as shown on page 4.
Step 2: Connect water supply
IMPORTANT: Do not rely on Bradley's
Drench Shower to support supply piping.
1. Connect water supply piping to 1" NPT inlet
on unit (piping supplied by installer). Provide
adequate supports (supplied by installer) for
supply pipe using pipe hangers or other means.
2. Thread the showerhead assembly onto the elbow
(Item 3). The showerhead shell will be held in
place by the springs.
3. Mount the safety sign to the wall using sign-
mounting hardware supplied by installer.
Ceiling
Tile
Showerhead
Shell
Showerhead
Assembly
Bradley Corporation • 215-148FM Rev. M; ECN 08-518
Spring
Bracket
Spring
Ring
Ø 5" (127mm)
1-7/8"
(48mm)
11-1/8"
(283mm)
Specify ceiling height
4-1/2" to 6"
(114mm to 152mm)
Ø 5-7/8"
(149mm)
9" (229mm)
9/11/08
S19-120FM
2" (51mm)
2"
(51mm)
Ø 5/16" (8mm)
(2) places
Ø 3-1/4"
(83mm)
4"
(102mm)
minimum
8-1/2"
(216mm)
minimum
False ceiling
maximum
thickness
2" (51mm)
3

Publicidad

Tabla de contenido
loading

Tabla de contenido