Installation Place

A place which provides the spaces around the indoor unit as
shown in the diagram
A place where there are no obstacles near the air inlet and outlet
A place which allows easy installation of the piping to the outdoor
unit
A place which allows the front panel to be opened
The indoor unit should be installed as top of the indoor unit
comes to at least 2 m height. Also, it must be avoided to put
anything on the top of the indoor unit.
CAUTION
Direct sunlight to the indoor unit's wireless receiver should be
avoided.
The microprocessor in the indoor unit should not be too close
to RF noise sources.
(For details, see the owner's manual.)
Remote control
A place where there are no obstacles such as a curtain that may
block the signal from the indoor unit
Do not install the remote control in a place exposed to direct
sunlight or close to a heating source such as a stove.
Keep the remote control at least 1 m apar t from the nearest TV
set or stereo equipment. (This is necessary to prevent image
disturbances or noise interference.)
The location of the remote control should be determined as
shown below.
i t
(Top view)
(Side view)
n
u
r

Indoor unit

7  m 
o
o
d
I n
     °
   7    5
Remote
Reception
control
range
* : Axial distance
INDOOR UNIT
5   
  m
m  
   5
   °
4   5  
4  5
°    
R    e  
c   e  
 p   t   
i    o  
n  
r   a  
Remote control
n    g  
e  
Cutting a Hole and Mounting
Installation Plate
Cutting a hole
When installing the refrigerant pipes from the rear
The center of the pipe hole
is above the arrow.
1. After determining the pipe hole position on the mounting plate
(
A
), drill the pipe hole (
the outdoor side.
NOTE
When drilling a wall that contains a metal lath, wire lath or metal
plate, be sure to use a pipe hole brim ring sold separately.
Mounting the installation plate
Anchor bolt holes
Hook 
  m
170
   7
   *
85
Hook 
Pipe hole
Indoor unit
Pipe hole
65 mm
100 mm
65 mm) at a slight downward slant to
Hook 
Pipe hole
Thread
7
 Mounting screw
Weight
62
82.5
r
o
o
f l
m
o
f r
r e
o
m
r
o
1
m
2