Final Steps - Interlogix TruPortal TP-ADD-2D Serie Referencia Rápida

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Door Contact Detail and Request to Exit
2
3
1 kΩ
Callout
Description
1
Typical door contact
circuit (dual EOL)
2
Door contact input
3
COM/shared

Final Steps

1.
Ensure the reader voltage jumpers match your specific readers.
2.
Apply power to the unit and listen for the relays to click, verifying
LED indicators for correct board operation.
3.
When finished, ensure all wires are clear and secure of the cover
before closing.
TruPortal Dual Door Interface Quick Reference
1
4
5
1 kΩ
Callout
Description
4
Install resistors
close to the door
contact
5
Door contact (must
match/follow the
door state)
Specifications
The TP-ADD-2D is for use in low voltage, Class 2 circuits only. These
specifications are subject to change without notice.
Incoming power ratings: 12 VDC, 300 mA max
Outputs
-
Four outputs: Relay type
-
Door strike: 24 VDC/1A
-
Aux: 24 VDC/0.1A
Inputs
-
Eight (8) unsupervised/supervised, standard EOL, 1k/1k ohm,
1% 1/4 watt
-
One (1) unsupervised, dedicated for cabinet tamper
Reader interface
-
Four interfaces
-
Reader power (jumper selectable): 12 VDC + 10% regulated,
125 mA maximum each reader or 5 VDC + 10% regulated,
600 mA maximum each reader
Communication: SNAPP bus
Cable requirements
-
Power: 18 AWG (1.024 mm / 0.823 mm
-
Reader data: 6 conductors, 18 AWG (1.024 mm / 0.823 mm
500 feet (150 m) maximum
-
SNAPP bus (RS-485): 22 AWG (0.644 mm / 0.326 mm
100 ohm impedance, twisted pair with shield, 4000 feet
(1219 m) maximum
Mechanical
-
Dimensions: 5.75 x 4.25 x 1 in. (146 x 108 x 25 mm)
Environmental
-
Temperature: 32 to 120° F (0 to 49° C )
-
Humidity: 5 to 85% RHNC at 77° F (25° C)
-
BTU Output: 12.3 BTU/hour
Certifications
-
CE marking
-
RoHS compliant
-
WEEE
3
2
), 1 stranded
2
),
P/N 460802991B 26JAN12 en-US
2
),

Publicidad

Tabla de contenido
loading