TECHNICAL CHARACTERISTICS

Auxiliary supply
Rated voltage Us
Operating limits
Frequency
Maximum consumption
Maximum dissipation
Immunity time for microbreakings
Voltage inputs
Maximum rated voltage Ue
UL rating
Measuring range
Frequency range
Measuring method
Measuring input impedance
Wiring mode
Current inputs
Rated current Ie
Measuring range
UL rating
Measuring method
Overload capacity
Overload peak
Dynamic limit
Self-consumption
Measuring accuracy
Measuring conditions
Voltage
Current
Frequency
Apparent power
Active power
Reactive power
– A load-break switch or circuit breaker
must be included in the electrical
installation of the building.
– It must be installled close by the
equipment and within easy reach of the
operator
– It must be marked the disconnecting
device of the equipment:
IEC/ EN 61010-1 § 6.12.2.1
This equipment must be installed by
qualified personnel, in compliance with
regulations in force for electrical systems, to
avoid damages or safety hazards.
The pfoducts, illustrated in this document,
are subject to be revised or improved at any
moment. Technical data and descriptions do
not therefore have any contractual value.
208-240VAC
154-288VAC
45-65Hz
5.5VA (Us=240VAC)
2.5W (Us= 240VAC)
20ms
690VAC phase-phase
400VAC phase-neutral
600VAC phase-phase
347VAC phase-neutral
60-830VAC phase-phase
30-480VAC phase-neutral
45-65Hz
True RMS
>1.1MΩ phase-phase and >570KΩ phase-neutral
Single-phase, two-phase, three-phase and
balanced three-phase.
5A (1A on request)
0.05-6A
Supplied by an external current transformer
(low voltage). 5A max
True RMS
+20% Ie from external CT with 5A secondary
50A for 1 second
125A for 10ms
<0.6W per phase
Temperature +23°C ±1°C
Relative humidity 45±15%
Voltage 0.2 - 1.2 Ue
Current 0.2 - 1.2 Ie
Class 0.5 ±0.35% full scale (830VAC)
Class 0.5 ±0.5% full scale (6A)
±0.1Hz
±0.5% full scale ±1digit
±1% full scale ±1digit (cosϕ. 0.7 - 1)
±1.25% full scale ±1digit (cosϕ. 0.3 - 0.7)
±1% full scale ±1digit (sineϕ. 0.7 - 1)
±1.25% full scale ±1digit (sineϕ. 0.3 - 0.7)
Additional errors
Voltage
Current
Insulation
Rated insulation voltage (Ui)
compliant with IEC/EN 61010-1
Ambient operating conditions
Operating temperature
Storage temperature
Relative humidity
Max pollution degree
Connections
Terminal type
Cable cross section (min-max)
Tightening torque
Housing
Material
Version
Dimensions w x h x d
Cutout
Degree of protection
Weight
Certifications and compliance
Certifications obtained:
Comply with standards:
UL Marking
±0.005% full scale / °C (-20...+60°C)
±0.015% full scale / °C (-20...+60°C)
690V
-20...+60°C
-30...+80°C
<90%
2
DMK 20
DMK 50
Plug-in
Fixed
2
2
0.2-2.5 mm
0.2-1.5 mm
(24-12 AWG)
(24-16 AWG)
0.5 Nm (4.5 lbin)
0.45 Nm (4 lbin)
DMK 20
DMK 50
Noryl SE1-GNF2 black
Noryl SE1 grey
self-extinguishing
self-extinguishing
Noryl
Noryl
Flush mount per
35mm rail mounting
IEC 61554
EN50022 6x17.5mm
modules
96 x 96 x 76mm
105 x 90 x 60mm
91 x 91mm
IP54 on front,
IP41 on front
IP20 on back
IP20 housing and
terminal blocks
434g
398g
cULus, GOST.
IEC/EN 61010-1, IEC/EN 61000-6-2,
CISPR 11/EN 55011, IEC/EN 61000-3-2,
IEC/EN 61000-3-3, IEC/EN 60068-2-61,
IEC/EN60068-2-27, IEC/EN60068-2-6,
UL508, C22.2 N°14-95.
– These Devices shall be protected by Any
Listed Fuses, Miscellaneous, Miniature and
Micro (JDYX) 15A Fuses on voltage input
phases.
– "Use 60°C/75°C copper (CU) conductor and
wire size range 18-12 AWG, stranded or
solid".
– "For use on a flat surface of a Type 1
Enclosure".