Lutron EcoSystem Guia De Instalacion página 11

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EcoSystem
CCI Troubleshooting Mode
When all eight OPT Switches are in the OFF position, the
LEDs enter CCI troubleshooting mode, which shows the
status of the contact closure inputs. CCI troubleshooting
mode only affects the LED indicators, and does not affect
the normal function of the OPT switches. Therefore, when
in CCI troubleshooting mode, all ballasts and modules
on the EcoSystem Bus will be in the override off state
and programming will be disabled via the EcoSystem
Programmer.
LED Indicator
V
PWR
STAT
BUS
(green)
ERR/EMERG
(green)
BUS
(blue)
ERR/EMERG
(blue)
Lutron | 
| Bus Supply Installation Guide
TM
Function in CCI Troubleshooting Mode
ON = Mains voltage present (always on)
ON = CCI-EMERG closed
OFF = CCI-EMERG open
ON = CCI-2 closed
OFF = CCI-2 open
ON = CCI-1 closed
OFF = CCI-1 open
ON = CCI-2 closed
OFF = CCI-2 open
ON = CCI-1 closed
OFF = CCI-1 open
See the table below to determine the association
between contact closure inputs and LEDs when in the
CCI troubleshooting mode. The corresponding LED will
turn ON when the corresponding contact closure is
closed.
EcoSystem
TM
 Bus Supply Installation Guide

Publicidad

Tabla de contenido
loading

Tabla de contenido