PowPak | Installation
Control Module with EcoSystem
Part of the Vive Family
RMJS-ECO32-SZ
120 – 277 V~ 50 / 60 Hz 80 mA
EcoSystem / DALI Control: 18 V-
Guaranteed Supply Current: 64 mA
Maximum Supply Current: 250 mA
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes.
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F and 104 °F (0 °C and 40 °C) ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
PowPak
Control Module
Install in center of room
to maximize RF coverage.
Radio Powr
Savr Occupancy
Sensor
PowPak
30 ft (9 m)
Control
maximum
Module
Pico
Remote
Control
All Wireless Transmitters must be installed within 30 ft (9 m) of
the PowPak Control Module with EcoSystem technology.
Default Functionality
Occupancy Sensors
Occupied: All lights 100%.
Unoccupied: All lights off.
Daylight Sensor
All lights dim in response to daylight.
Link
Cal.
Test
Wireless Controls
On
All lights 100%
Favorite All lights 50%
Off
All lights off
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036
Required Components
For each system, ensure that you have:
One PowPak Control Module
At least one Wireless Transmitter
041588
041695
Rev. A
Rev. A
04/2019
04/2019
Top LED
Raise
+
Toggle
Lower
Bottom
LED
Radio Powr Savr Occupancy/Vacancy Sensor
(10 maximum)
Start Here
Mount, Wire, and Install EcoSystem
1
Devices and Lighting Fixtures
Consult third-party device installation guide
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit
breaker before installing the unit.
A
Connect mains wiring (hot, neutral) to each fixture.
B
Connect EcoSystem control to each fixture.
Neutral
Line/Hot
+
E1 / DA+
E2 / DA-
To additional EcoSystem fixtures
Programming with a Vive Hub
3
A
B
Use an iOS or Android compatible device.
Vive
X
Troubleshooting
Ballasts cannot be controlled locally from PowPak Control Module
with EcoSystem technology.
Lights do not respond to Wireless Transmitter(s).
Lights are unstable at low-end or flash/flicker at turn-on or turn-off. • Adjust the low-end trim.
Wireless Transmitter(s) cannot be associated to PowPak Control
Module with EcoSystem technology.
Pico Remote Control
(10 maximum)
Install PowPak Control Module with
2
EcoSystem technology
Suggested Installation Location: Center of room to
ensure proper RF coverage of area.
A
The PowPak Control Module can be installed on a junction box or
marshalling box using the conduit nut (provided) or with mounting
screws (provided) and must be installed away from a fixture/troffer.
The device must NOT be mounted inside or on a fixture/troffer or other
metallic enclosure. Please consult local and national electric codes for
proper installation.
NEU
B
Once installed, energize the PowPak Control Module.
Sample LED
C
Use the Toggle " u " , Raise "▲" and Lower " " buttons to verify
HOT
driver shown
control wiring.
Wire Gauge
Total Digital Link Wire Length
E1
E2
EcoSystem
12 AWG (4.0 mm
)
2200 ft (671 m)
2
14 AWG (2.5 mm
2
)
1400 ft (427 m)
16 AWG (1.5 mm
2
)
900 ft (275 m)
18 AWG (1.0 mm
)
570 ft (175 m)
2
C
Download the Lutron Vive app.
Open the app and follow the instructions.
• Ensure that the breaker(s) to the PowPak Control Module are energized.
• Ensure that the EcoSystem control lines are wired to the lighting fixture(s).
Reset to factory defaults.
• Ensure that the breaker(s) to the PowPak Control Module and drivers/ballasts are energized.
• Ensure that Wireless Transmitters are associated to the PowPak Control Module.
• Ensure that Wireless Transmitter(s) are within 30 ft (9 m) of the PowPak Control Module.
Reset to factory defaults.
• Ensure that Wireless Transmitter(s) are within 30 ft (9 m) of the PowPak Control Module.
• The maximum number of Wireless Transmitters have been associated to the PowPak Control Module. To remove a previously set up Wireless Transmitter, tap a
Wireless Transmitter button three times; on the third tap hold for three seconds and then tap three more times.
Customer Assistance www.lutron.com/support
At least one EcoSystem LED Driver or Fluorescent Ballast
This device can be installed on a junction box or marshalling box using the conduit nut or with mounting
screws and must be installed away from a fixture/troffer. The device must NOT be mounted inside
or on a fixture/troffer or other metallic enclosure. Improper installation can result in degraded wireless
communication, intermittent or sustained communication failures, and will not be covered under
warranty.
For applications where code requires the PowPak fixture control to be installed inside an additional
junction box (e.g., U.S.A.), please see Lutron Application Note #423 (P/N 048423) at www.lutron.com.
+
Link
Cal.
Test
64 mA guaranteed for the control lines. May be pre-installed in light fixture.
Radio Powr Savr Daylight Sensor
Note: All drivers and ballasts used with Vive wireless controls must comply with the limits
(1 maximum)
for a Class A device, pursuant to Part 15 of the FCC rules.
Line / Hot (Black)
Neutral (White)
DALI
984 ft (300 m)*
984 ft (300 m)*
900 ft (275 m)
570 ft (175 m)
* Maximum recommended length as per IEC 62386-101 Ed. 2.0
Note: For further information on set up, programming, and troubleshooting with a Vive
system, please refer to the installation instructions included with the Vive hub or visit
www.lutron.com/vive
Note: For programming the PowPak Control Module with EcoSystem technology
vive.lutron.com
X
without a Vive hub see reverse side
E1 / DA+ (Violet)
EcoSystem to Fixtures
E2 / DA- (Violet/White)
.
www.lutron.com / vive

Publicidad

loading

Resumen de contenidos para Lutron PowPak RMJS-ECO32-SZ

  • Página 1 120 – 277 V~ 50 / 60 Hz 80 mA For applications where code requires the PowPak fixture control to be installed inside an additional junction box (e.g., U.S.A.), please see Lutron Application Note #423 (P/N 048423) at www.lutron.com. Toggle Link Cal.
  • Página 2 Cisco in the U.S. and other countries and is used under license. Android, Google Play and the Google Play logo are trademarks of Google Inc. DALI is a trademark of ZVEI. ©2013 –...
  • Página 3 Concernant les applications pour lesquels le code exige l’installation de la commande de luminaire PowPak à RMJS-ECO32-SZ 120 – 277 V~ 50 / 60 Hz 80 mA l’intérieur d’un boîtier de raccordement supplémentaire (p. ex. aux États-Unis), veuillez consulter la note d’application Alterner nº 423 de Lutron (nº de pièce 048423) sur www.lutron.com. Link Cal. Baisser Test Commande EcoSystem / DALI : 18 V- Courant d’alimentation garanti : 64 mA...
  • Página 4 Cisco aux États-Unis et dans d’autres pays, utilisée sous licence. Android, Google Play et le logo Google Play sont des marques commerciales de Google Inc. DALI est une marque commerciale de ZVEI. ©2013 –...
  • Página 5: Componentes Requeridos

    Para las aplicaciones donde la normativa requiera que el control del artefactos PowPak sea instalado dentro de una caja de RMJS-ECO32-SZ 120 – 277 V~ 50 / 60 Hz 80 mA conexiones adicional (p. ej., en E.U.A.) consulte la Nota de aplicación Nº 423 (N/P 048423) de Lutron en www.lutron.com. Alternar Link Cal.
  • Página 6 Lutron, Pico, Vive, EcoSystem y PowPak son marcas comerciales de Lutron Electronics Co., Inc. registradas en E.U.A. y otros países. Radio Powr Savr es una marca comercial de Lutron Electronics Co., Inc. App Store es una marca comercial de Apple Inc.,...