2.3 ELECTRICAL CONNECTION OF THE UNIT

CAUTION: always disconnect the unit from the mains before carrying out any operation on electric parts.
Accomplish following recommendations:
• Connect the unit to an efficient ground cable as required by the in force being norms.
• Check the data on the unit's name plate and select the correct cable section according to working amperage.
• Dimension the power supply cable so that voltage drop at start-up does not exceed 10% of nominal voltage.
• The on charge of the customer installed power supply cable must be a double insulated one.
• Before unit's start-up make sure that mains voltage and frequency correspond to those ones indicated on the unit's
name plate.

2.4 WIRING PLAN

2.5 TECHNICAL DATA

MODEL
RATED VOLTAGE
MIN. CURRENT
MIN. POWER
MAX. CURRENT
MAX. POWER
PROTECTION
EVAPORATIVE
CAPACITY

2.6 MAINTENANCE

CAUTION: ATTENTION: Before effecting any type of intervention disconnect the unit.
Cleaning operations and their frequency do depend on the specific working environment.
Check terminals and connections
L
PE
N
KCE34.00
110/240V 50HZ
110/240V 60HZ
230/1/50HZ
0,2 A
40 W
0,8 A
180 W
FUSE 4gG
34 g/h
½ year
110/240V 50HZ
13
KCE67.00
110/240V 60HZ
230/1/50HZ
0,4 A
80 W
1,6 A
360W
FUSE 4gG
67 g/h