Technical Manual
Use Ambient Air
The monobloc unit may also be placed in a heated room, but the air flow must be directed to an unheated
room. Bear in mind that because of air flow, cooling the unheated room can affect the adjacent heated
rooms.
A – Unheated area minimum 50m
B – Heated area or unheated area;
Ducts used to direct the airflow are not included in the equipment, and it is up to the
installer to install them, if necessary, to comply with the manufacturer's recommen-
dations.
Diameter of pipes must be of 160 mm.
Each of the ducts (air inlet or outlet) should not exceed 8m in length, or the total
static loss of the installation should not exceed the static fan pressure (60Pa).
;
3
MONOBLOC 100L
43