Setup & Commissioning
Test mode
• Ensure that the sensor is in test
mode.
- set time delay to minimum
setting of 15 seconds
- set light level to maximum
("day" setting, light level function
overridden - factory setting)
• Turn power ON at the circuit
breaker (lights will turn ON). After
a warm up period of up to one
minute, lights will turn OFF if the
sensor does not detect motion.
• Walk in view of sensor, lights should
turn ON. Be still for 15 seconds and
lights should turn OFF.
Light level
The light level feature allows lighting
to remain OFF during daylight,
regardless of occupancy. Daytime
operation is at 200 footcandles
(factory setting). Nighttime operation
is at .2 footcandles.
ON
High
Low
1 2 3 4
Light level: .2 (night) to 200 (day) footcandles
Light level teach mode
The light level teach mode reads the
ambient light level in the space and
selects this amount for the light level
setting.
• Turn the light level setting to
• After 10 seconds, the value of the
ambient brightness is saved.
• This value is also available after a
power failure if the potentiometer is
set to teach mode at power up.
Time delay
Time delay is the period of time lights
remain on after the last detection.
Adjustment ranges from 15 seconds
to 30 minutes. Factory setting is
15 minutes.
ON
Low
1 2 3 4
Time Delay DIP Switch
1
2
3
4
Time
ON
ON
ON
OFF
15 sec
ON
OFF
OFF
OFF
1 min
OFF
ON
ON
OFF
5 min
ON
OFF
ON
OFF
10 min
ON
ON
OFF
OFF
15 min
OFF
ON
OFF
OFF
20 min
OFF
OFF
ON
OFF
25 min
OFF
OFF
OFF
OFF
30 min
N/A
N/A
N/A
ON
override
After setup and commissioning tests
are complete, adjust the time delay
and light level settings to fit the
application needs.
Low
- 8 -
Setup & Commissioning
HBS 300 (347-480V)
The HBS 300 (347-480V) contains
three pyroelectric sensors to detect
occupancy. At an installation height
of 8 to 45 feet, maximum reach is
22 feet radial and 60 feet tangential.
If needed, the detection zone can be
adjusted (see below).
Coverage may vary depending on
mounting height and environmental
High
conditions.
HBS 200 (347-480V) Coverage
The HBS 200 (347-480V) contains
two pyroelectric sensors to detect
occupancy and has an aisle way
coverage of up to 100 feet when
mounted at 40 ft. If needed, the
detection zone can be adjusted
with a lens cover (see below).
In addition, the view of the HBS 200
(347-480V) can be rotated 90 degrees.
High
To do this, remove the sensor housing
from the back box by pressing the
tabs on either side of the sensor.
Coverage may vary depending on
mounting height and environmental
conditions.
LC3
10ft/3m
20ft/6.1m
30ft/9.1m
40ft/12.2m
50ft 40ft
35ft
35ft
40ft
15.2m12.2m
10.7m
10.7m
12.2m
22ft
22ft
6.7m 6.7m
Aisle
LC3
10ft/3m
20ft/6.1m
30ft/9.1m
40ft/12.2m
50ft
50ft
15.2m
15.2m
53ft
53ft
16.2m
16.2m
radial
tangential
- 9 -
50ft
15.2m