WIKA FSD-4 Manual De Instrucciones página 16

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. Commissioning, operation
5.5 Overview of parameters
Menu
Description
item
EN
INI
Initialisation menu
UNIF
Flow unit
TIF
Min / Max flow setting, only active with UNIF = %
Zero point setting /"Autozero" version, only active
0SET
when UNIF ≠ %
mu_F
Flow multiplier, only active when UNIF ≠ %
uniT
Temperature unit
PIPD
Pipeline diameter in mm, only active when UNIF ≠ %
SP1 / SP2
Hysteresis function: Switch point (switching output 1
if applicable 2)
FH1 / FH2
Window function
Window high (switching output 1, if applicable 2)
RP1 / RP2
Hysteresis function: Reset point (switching output 1,
if applicable 2)
FL1 / FL2
Window function
Window low (switching output 1, if applicable 2)
EF
Extended programming functions
RES
Reset the parameters to factory setting
DS1 /
Switching delay time, which must occur without
DS2
interruption before any electrical signal change occurs
(SP1, if applicable SP2)
16
Parameter
-
m/s, l/min, m3/h(m³/h), FT/s, FT3m (ft³/s),
UGPm (US Gal/min), GPm (Imp. Gal/min), %
MIN (NO/YES) sets current flow value to 0 %
MAX (NO/YES) sets current flow value to 100 %
YES/NO
YES sets current flow value to zero
0.10 ... 10.00
°C, °F
10 ... 1,000
0.05 ... 3 m/s [0.17... 9.84 ft/s]
1.7 ... 100 %
If SP2 is configured for temperature:
-18.2 ... +85 °C [-0.8 ... +185 °F]
-
0 ... 2.950 m/s [0 ... 9.67 ft/s]
0 ... 98.3 %
If SP2 is configured for temperature:
-20 ... +78.2 °C [-4 ... +172.8 °F]
-
-
YES/NO
0.00 ... 65.00 s
WIKA operating instructions flow switch, model FSD-4
Factory
setting
-
m/s
-
-
1.00
°C
25
3.000 (m/s)
-
2.700 (m/s)
-
-
-
0.00 s

Publicidad

Tabla de contenido
loading

Tabla de contenido