Casals REINTAIR S 300 AC Manual De Uso Y Mantenimiento página 53

Purificador de aire sin instalación
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Record 2: Operation status on / off (manual mode) [read / write].
0: Off.
1: On.
Default value: 0 [Off].
= 240 (0xF0): Default values.
= 255 (0xFF): Reset.
Record 3: Fan speed setpoint [read / write].
The value that is sent is the speed value (0% to 100%) in 16-bit binary.
Default value: 70 [70%: Fan on].
Record Set fan speed period 1 (time programming) [read / write].
The value that is sent is the speed value (0% to 100%) in 16-bit binary.
Default value: 50 [50%: Fan on].
Record 5: Set fan speed period 2 (time programming) [read / write].
The value that is sent is the speed value (0% to 100%) in 16-bit binary.
Default value: 30 [30%: Fan on].
Record 6: Setpoint fan speed reduced period (time programming) [read / write].
The value that is sent is the speed value (0% to 100%) in 16-bit binary.
Default value: 0 [0%: Fan off].
Record 7: Minimum fan speed voltage [read / write].
The value that is sent is the voltage value (0.0V to 5.0V) multiplied by 10 in 16-bit binary.
Default value: 20 [2,0V].
Record 8: Maximum fan speed voltage [read / write].
The value that is sent is the voltage value (6.0V to 10.0V) multiplied by 10 in 16-bit binary.
Default value: 95 [9,5V].
Record 9: G4 filter operating time Hours [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0h to 65000h. The value of 65000h does not overflow) in 16-bit binary.
Default value: 0 [0h].
Record 10: G4 filter operating time Minutes [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0min to 59min) in 16-bit binary.
Default value: 0 [0min].
Note: The operating time (Registers 9 and 10) only increases if the fan is operating (Register 51 ≠ 0),
Registro 11: Horas de funcionamiento filtro G4 para indicación de filtro sucio (timer) [lectura/escritura].
El valor que se envía es el valor de las horas (función deshabilitada: 0, 1h a 9000h) en binario de 16 bits.
Valor por defecto: 4000 [función habilitada, e indicación de filtro sucio G4 con horas de funcionamiento ≥ 4000h].
=0: Función deshabilitada.
>0: Función habilitada.
Record 12: H14 filter operating time Hours [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0h to 65000h. The value of 65000h does not overflow) in 16-bit binary.
Default value: 0 [0h].
Record 13: H14 filter operating time Minutes [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0min to 59min) in 16-bit binary.
Default value: 0 [0min].
Note: The operating time (Registers 12 and 13) only increases if the fan is operating (Register 51 ≠ 0),
Record 14: Hours of operation of H14 filter for indication of dirty filter (timer) [read / write].
The value that is sent is the value of the hours (function disabled: 0, 1h to 9000h) in 16-bit binary.
Default value: 7305 [function enabled, and indication of dirty filter H14 with operating hours ≥ 7305h].
= 0: Function disabled.
> 0: Function enabled.
29
CV05_2020-Rev.01

Publicidad

Capítulos

Tabla de contenido
loading

Productos relacionados para Casals REINTAIR S 300 AC

Tabla de contenido