Fan operation (voltage):
OFF 0.0V
ON
0% 0.0V
1% Minimum voltage (Record7)
...
100% Maximum voltage (Record 8) End of line resistance configuration
Fan operation
Record 52: Filter status (by timer) [read-only].
High byte: G4 filter.
0: Filter clean.
1: Dirty filter.
Low byte: H14 filter.
0: Filter clean.
1: Dirty filter.
Record 53: Current status UV-C lamp [read only].
0: Off (UV-C lamp deactivated - relay contact open).
1: On (UV-C lamp activated - relay contact closed).
UV-C lamp operation
Record 54: Firmware version [read-only].
The value that is sent is the value of the controller software version (XX.X) multiplied by 10 in 16-bit binary.
Note: When powering the regulator, or after a reset, it displays the firmware version on the display (v X.X).