6.3.2 Signal relays
The motor has two outputs for potential-free signals via two internal
relays. You can set the signal outputs to Operation, Pump
running, Ready, Alarm and Warning.
Grundfos Eye is off
The power is off.
Operation
Pump running
C
NO
NC
C
NO
NC
Grundfos Eye is rotating green
The pump or motor runs in Normal mode in open or closed loop.
10
Type
Function
Normally closed contact
Common
Signal relay 1. LIVE or PELV.
Normally open contact
Normally closed contact
Common
Signal relay 2. PELV only.
Normally open contact
Digital input/output, configurable.
DI3/OC1
Open collector: Maximum 24 V resistive or inductive.
Analog input:
AI1
0-20 mA or 4-20 mA
0.5-3.5 V, 0-5 V or 0-10 V.
Digital input, configurable.
DI1
+5 V
Power supply to a potentiometer or sensor.
GND
Ground.
GENIbus, A
GENIbus, A (+).
GENIbus, Y
GENIbus, Y (GND).
GENIbus, B
GENIbus, B (-).
GND
Ground.
+24 V
Power supply.
+24 V
Power supply.
+5 V
Power supply to potentiometer and sensor.
GND
Ground.
GDS TX
Grundfos Digital Sensor output.
GDS RX
Grundfos Digital Sensor input.
Analog input:
AI2
0-20 mA or 4-20 mA.
0.5 - 3.5 V, 0-5 V or 0-10 V.
Ready
C
NO
NC
Digital input 1 is factory-set to be start or stop input where an open circuit
results in stop. A jumper has been factory-fitted between terminals 2 and
6. Remove the jumper if digital input 1 is to be used as external start or
stop or any other external function.
The functions of the two signal relays appear from the table below:
Alarm
Warning
C
NO
NC
C
NO
Operating mode
-
NC