Notes
These figures (*) are for readers powered from the controller. The cable distances
can be increased to 1650' / 500m by locally powering the readers.
Locally powered readers must be connected to a UL 603 power limited Class 2
supply for US, or a ULC S318 power limited Class 2 supply for Canada.
If you use 22AWG / 0.34mm² cables, twist the wires and double them over before
inserting them in the crimps.
Maximum cable distances will be less for readers which have been set to give
Wiegand output.
Specification
Reader Range
Up to 4.0" / 100mm
Temperature
Operating
-40°C — +66°C / -40°F — +151°F
Humidity
Operating for 24 hours
10-85% RH @ 30±2°C / 85±4°F
Ingress Protection
IP65 after installation — evaluated by lab separate from UL. Installer must adequately seal any
connections made.
Power
12V — +24V
Storage
-40°C — +66°C / -40°F — +151°F
Tested at 93% for ULC S319.