6.2 Requirements of arrangement space of the unit
1) To ensure adequate airflow entering the condenser, the influence of descending airflow caused by the high-rise buildings
around upon the unit should be taken into account when installing the unit.
2) If the unit is installed where the flowing speed of air is high, such as on the exposed roof, the measures including sunk fence
and Persian blinds can be taken, to prevent the turbulent flow from disturbing the air entering the unit. If the unit needs to be
provided with sunk fence, the height of the latter should not be more than that of the former; if Persian blinds are required, the
total loss of static pressure should be less than the static pressure outside the fan. The space between the unit and sunk fence
or Persian blinds should also meet the requirement
3) If the unit needs to operate in winter, and the installation site may be covered by snow, the unit should be located higher than
the snow surface, to ensure that air flows through the coils smoothy.
A
Main unit
A
Table 6-2
A
B
C
D
Input of airow
D
Input of airow
Fig. 6-3 single unit installstion
Input of airow
E
Main unit
Main unit
E
Main unit
Main unit
E
Main unit
Main unit
Input of airow
Fig. 6-4 multiple units installstion
Installation space (mm)
≥800
≥2000
≥2000
≥800
07
Input of airow
Main unit
E
Main unit
E
D
Main unit
E
Main unit
E
F
G
/
Input of airow
≥800
≥1100
≥6000
/
V.1