Processing :
ADC :
Response time (10..90 %) :
Transmission :
Max
Transmission error
Resolution :
Thermal Drift :
Insulation Voltage :
Protection Index :
Operating Conditions :
Storage Temperature :
LED Signalling :
Connections :
Conductor Section :
Wire stripping :
Box :
Dimensions, Weight :
Standards :
(3)
Referred to the physical full scale (see table INPUT SIGNAL AND SCALE DETAILS
contained in the
SETTINGS OF THE DIP-SWITCHES
with the shunt release detection function disabled, and after at least 3 minutes of operation.
Digital, Calculation in floating-point 32 bit.
14 bit on the total measuring range (bipolar).
At 50 Hz: max 25 ms without filter and 55 ms with filter.
At 60 Hz: max 23 ms without filter and 51 ms with filter.
Optical-Digital.
(3)
For mA or 5 V output : 0,085% of the full scale value .
:
For 10 V output: 0,075% of the full scale value.
Voltage Output: 1 mV, Current Output: 2 A .
< 120 ppm/K.
1,5 kV between each group of ports.
IP20.
Temperature -20..+65 °C
Humidity 10..90 % at 40°C (non-condensing).
Altitude: up to 2000 m.a.s.l.
-40..+85 °C.
Fault, Over-Range or incorrect setting.
Spring terminals.
0,2..2,5 mm .
8 mm.
PBT (black colour).
6,2 x 93,1 x 102,5 mm, 46 g.
EN61000-6-4/2002 (electromagnetic emission, indust ial
surroundings)
EN61000-6-2/2005 (electromagnetic immunity, industrial
surroundings)
EN61010-1/2001 (safety)
All the circuits must be provided with double insulation
from the circuits under dangerous voltage. The power
supply transformer must be built to compliance with
EN60742: "Insulation transformers and Safety
transformers".
MI001211-E
2
section). Precision is guaranteed
m
r
ENGLISH - 2/8