Steam Line Installation Examples - Honeywell Home HM700ADISTKIT Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

HM700ADISTKIT

Steam Line Installation Examples

2 (51)
MINIMUM
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
BEFORE
ANY BEND
CONDENSATE
LINE
CONNECT
CONDENSATE
HOSE TO FILL
CUP
Fig. 3. Steam distributor above humidifier (hose).
Measurements in inches (mm).
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
BEFORE
ANY BEND
Fig. 4. Steam distributor below humidifier (hose).
Measurements in inches (mm).
For more information on maintenance and replacement, please visit http://honeywellhome.com
or call 1-800-468-1502 or 1-800-814-9452.
Resideo Inc., 1985 Douglas Drive North,
Golden Valley, MN 55422
www.resideo.com
33-00160EFS—05 M.S. Rev. 08-19 | Printed in United States
This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-468-1502
©2019 Resideo Technologies, Inc. The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved.
12 (305)
CONDENSATE
LINE
SUPPORT
BRACKETS
CONNECT
STEAM
HOSE TO
CYLINDER
SUPPORT
BRACKETS
12 (305)
MINIMUM
CONDENSATE
TRAP
TO DRAIN
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
BEFORE
ANY BEND
USE FULL SIZE CONDENSATE
TEE AT LOW POINT. SLOPE
LINES UP TO "T" AND
IMMEDIATELY AFTER IT.
1
HOSE WILL SOFTEN OVER TIME. PROPER SUPPORT IS NECESSARY.
M35717
Fig. 5. Steam distributor below humidifier with
obstruction (hose). Measurements in inches (mm).
CONDENSATE
TRAP NOT 12
(305) BELOW
DISTRIBUTOR
M35718
Fig. 6. Common steam line installation errors.
Measurements in inches (mm).
1
SUPPORT
BRACKETS
OBSTRUCTION
12
(305)
2 (51)
MIN.
MINIMUM
TO DRAIN
TO DRAIN
NO
CONDENSATE
TRAP AT
VERTICAL
TRANSITION
STEAM LINE
NOT SLOPED
12 (305)
MINIMUM
M35719
M35720