Product
Instructions
Viega ProPress
For use only with Viega stainless steel tubing
1
4
5
7
Viega ProPress for Stainless Insertion Depth Chart
Pipe Size
½"
Insertion Depth
¾"
CAUTION
It is the responsibility of designers of piping
systems to verify the suitability of type 304 and 316 stainless steel
pipe for use with the intended fluid media. The fluid's chemical
composition, pH level, operation temperature, chloride level, oxygen
level, and flow rate and their effect on AISI type 316 stainless steel
must be evaluated by the material specifier to confirm system life
will be adequate for the intended service. Failure to do so may
cause serious personal injury or property damage. Contact Viega
Technical Services for questions and approvals.
This document subject to updates. For the most current Viega technical literature please visit www.viega.us.
Click Services -> Click Electronic Literature Downloads -> Select Product Line -> Select Desired Document
Viega LLC, 100 N. Broadway, 6
PI-PPS 518526 0515 (EN ES FR)
for Stainless ½" to 2"
®
2
8
¾"
1"
1¼"
1½"
/
"
/
"
1"
1
/
7
7
7
8
8
16
Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618
th
for installing Viega ProPress for Stainless fittings. Failure
to follow all instructions may result in extensive property
damage, serious injury or death.
1. Cut stainless steel tubing only with an approved stainless steel
pipe cutting tool. Cut tubing at right angle to permit proper
3
joining with the fitting.
2. Remove burr from inside and outside of tubing to prevent
damage to the sealing element.
3. Check seal for correct fit. Do not use oils or lubricants. Use
only Viega ProPress Shiny Black EPDM or Dull Black FKM
sealing elements.
4. Mark proper insertion depth as indicated by the Viega
ProPress Insertion Depth Chart. Improper insertion depth may
6
result in improper seal.
5. While turning slightly, slide press fitting onto tubing to the
marked depth.
Note: End of tubing must contact stop.
6. Insert appropriate Viega jaw into the pressing tool and push in,
holding pin until it locks in place.
7. Open the jaw and place at right angles on the fitting. Visually
check insertion depth using mark on tubing.
8. Start pressing process and hold the trigger until the jaw has
9
engaged the fitting.
9. After pressing, the jaw can be opened again.
2"
"
1
/
"
9
16
pressures. When testing with compressed air the proper
pressure range is ½ psi to 45 psi maximum. Following a
successful leak test, the system may be pressure tested up
to 200 psi with air, or up to 600 psi with water, if required by
local code requirements or project specifications.
Read, understand and follow all instructions
Leak Testing with Smart Connect
Unpressed connections are located by
pressurizing the system with air or water.
When testing with water the proper pressure
range is 15 psi to 85 psi maximum. Leak
testing with air can be dangerous at high
®
:
1 of 2

Publicidad

loading

Resumen de contenidos para Viega ProPress

  • Página 1 Contact Viega Technical Services for questions and approvals. This document subject to updates. For the most current Viega technical literature please visit www.viega.us. Click Services -> Click Electronic Literature Downloads -> Select Product Line -> Select Desired Document Viega LLC, 100 N.
  • Página 2 Este documento está sujeto a actualizaciones. Para consultar la más reciente literatura Ce document est soumis à des mises à jour. Pour consulter les manuels techniques Viega les técnica de Viega visitar www.viega.us. Hacer clic en Services -> Electronic Literature plus récents, consultez notre site www.viega.us.